Technical specifications for X20CS1070

  • Manufacturer:
    B&R
  • Part Number:
    X20CS1070
  • Product Family:
    B&R X20 System
  • Product Type:
    CAN Bus Communication Module
  • Stock:
    1
  • Interfaces:
    1 CAN bus
  • CAN connector:
    Via X20TB12
  • Maximum bus distance:
    1000 m
  • Maximum transfer rate:
    1 Mbit/s
  • CAN controller:
    SJA1000
  • Bus power consumption:
    0.01 W
  • Internal I/O power consumption:
    1.44 W
  • Electrical isolation:
    CAN isolated from bus and I/O power
  • Required terminal block:
    X20TB06 or X20TB12, ordered separately
  • Required bus module:
    X20BM11 or X20BM15, ordered separately
  • Module pitch:
    12.5 mm +0.2 mm
  • Mounting orientation:
    Horizontal or vertical
  • Degree of protection:
    IP20
  • Operating temperature:
    -25 to 60 °C horizontal; -25 to 50 °C vertical
  • Storage / transport temperature:
    -40 to 85 °C
  • Relative humidity:
    5 to 95%, non-condensing
  • Tariff Code:
    8538900000
  • Country of origin:
    Germany
  • Place of shipment:
    Xiamen, Fujian, China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals CAN Network Integration Diagnostics Application
  • Adds one CAN interface to an X20 station
  • Provides integrated CAN termination and galvanic isolation
  • Supports serial connection of complex remote devices

X20CS1070 is a B&R can bus communication module designed for the X20 System.

The module adds serial CAN communication to an X20 station so complex CAN devices can be connected through the controller application.

Before installation or replacement, verify the complete material number, CAN protocol and application requirements, bit rate, node addressing, X20TB12 pinout, termination state, cable length and topology, X20BM11 or X20BM15, Automation Studio configuration, and bus-load calculation.

Availability, condition, price, and shipping time for X20CS1070 are confirmed during quotation.

B&R X20CS1070 CAN Bus Communication Module Manuals, Datasheets, Links

Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.

  • Bit rate and node addresses are defined by the application
  • Maximum distance depends on bit rate and correct CAN topology
  • The integrated terminator should be enabled only at a physical segment end
  • The module may be positioned anywhere on the remote backplane
  • The Automation Studio project must match the installed slot
  • Application software defines the required CAN protocol handling
  • Run and error indicators report module state
  • Data-transfer indicators support commissioning
  • Termination status is visible for physical-layer checks
  • Connecting complex CAN devices to an X20 controller
  • Adding an application-managed CAN segment to a remote X20 station
  • Maintaining isolated CAN communication in modular machinery
Description
X20CS1070 is a B&R can bus communication module for the X20 System.

It provides one isolated CAN interface at up to 1 Mbit/s with an integrated terminating resistor and can be placed at any position on a remote X20 backplane.

Before installation or replacement, confirm the complete material number, CAN protocol and application requirements, bit rate, node addressing, X20TB12 pinout, termination state, cable length and topology, X20BM11 or X20BM15, Automation Studio configuration, and bus-load calculation.
Alternative Names
X20CS1070 X20 CS1070 B&R X20CS1070 B&R X20 CS1070 BR X20CS1070 B&R X20 System X20CS1070 X20 System X20CS1070
Technical notes
X20CS1070 provides one isolated CAN interface. Confirm the application protocol, bit rate, node addresses, terminal pinout, segment termination, cable topology, required bus module, and Automation Studio configuration before connecting field devices.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
Does B&R X20CS1070 automatically provide a high-level CAN protocol?
It provides the CAN interface; confirm that the controller application and libraries implement the protocol required by the connected devices.
Why can B&R X20CS1070 transmit but receive no valid frames?
Check bit rate, frame format, node IDs, termination, polarity, grounding, acceptance filtering, and whether the application is processing the correct CAN channel.
When should the integrated termination on B&R X20CS1070 be enabled?
Enable it only when the module is at a physical end of the CAN segment; the two segment ends should be terminated.
Can B&R X20CS1070 be installed in any X20 slot?
The official description allows placement anywhere on the remote backplane, but the project slot and required accessories must match the physical station.
Which accessories are required for B&R X20CS1070?
Confirm X20TB06 or X20TB12 and X20BM11 or X20BM15, ordered separately, plus suitable CAN cable and connectors.
What limits the practical CAN cable length with B&R X20CS1070?
Bit rate, cable impedance, topology, stubs, termination, shielding, grounding, and EMC conditions determine the usable distance.
What should be saved before replacing B&R X20CS1070?
Save the Automation Studio project, slot, CAN bit rate, protocol settings, node map, filters, termination state, wiring, and diagnostic captures.