X67AI1323

/ 4.9
1001 reviews | Need a Specific Revision?
B&R X67AI1323 is an IP67 X67 analog input module with four differential 0 to 20 mA or 4 to 20 mA channels and 12-bit conversion for the X67 System.
In Stock
Ships by Wednesday, October 28
Fast Shipping Available
Get a quick price for X67AI1323
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for X67AI1323

  • Manufacturer:
    B&R
  • Part Number:
    X67AI1323
  • Product Family:
    B&R X67 System
  • Product Type:
    4-channel Current Analog Input Module
  • Stock:
    1
  • Analog inputs:
    4 differential current channels
  • Input ranges:
    0 to 20 mA or 4 to 20 mA
  • Resolution:
    12-bit
  • Conversion time:
    400 µs for all inputs
  • Input load:
    <300 Ω
  • Maximum input current:
    ±30 mA
  • Voltage drop at 20 mA:
    Typically 4.5 V
  • Input filter:
    1 kHz, 40 dB
  • Common-mode range:
    ±11 V
  • Gain error:
    0.1%
  • Offset error:
    0.05%
  • Crosstalk:
    < -70 dB
  • Sensor supply:
    0.5 A total
  • Internal I/O / X2X power:
    3 W / 0.75 W
  • Degree of protection:
    IP67
  • Operating temperature:
    -25 to 60 °C
  • Storage / transport temperature:
    -40 to 85 °C
  • Dimensions:
    5.3 × 8.5 × 4.2 cm
  • Input connectors:
    4 × M12, A-coded
  • Weight:
    0.19 kg
  • Tariff Code:
    8538900000
  • Country of origin:
    Germany
  • Place of shipment:
    Xiamen, Fujian, China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Loop Power Field Wiring Wiring Application
  • Reads four differential 0–20 mA or 4–20 mA loops
  • Updates all channels in 400 microseconds
  • Provides sealed IP67 current acquisition near field transmitters

X67AI1323 is a B&R 4-channel current analog input module designed for the X67 System.

The module acquires distributed current-loop process signals near sensors and machine equipment.

Before installation or replacement, verify the complete material number, the 0 to 20 mA or 4 to 20 mA scaling, loop power and compliance voltage, differential wiring, M12 A-coded input pinout, common-mode voltage, open-loop behavior, X2X mapping and IP67 sealing.

Availability, condition, price, and shipping time for X67AI1323 are confirmed during quotation.

B&R X67AI1323 4-channel Current Analog Input Module Manuals, Datasheets, Links

Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.

  • The transmitter supply must provide enough compliance voltage for the complete loop
  • The module input burden is less than 300 ohms
  • Polarity and common-mode voltage must stay within the documented limits
  • Differential pairs should be routed away from switching power conductors
  • Shielding and grounding should avoid loop currents
  • Sealed M12 A-coded connectors and caps maintain IP67 protection
  • Differential pairs should be routed away from switching power conductors
  • Shielding and grounding should avoid loop currents
  • Sealed M8 connectors and caps maintain IP67 protection
  • Distributed 4–20 mA pressure, level and flow measurement
  • Machine-mounted 0–20 mA transducer acquisition
  • IP67 current-loop monitoring close to process equipment
Description
X67AI1323 is a B&R 4-channel current analog input module for the X67 System.

It converts all channels in 400 µs with a 1 kHz filter and presents less than 300 Ω input load for field-current transmitters.

Before installation or replacement, confirm the complete material number, the 0 to 20 mA or 4 to 20 mA scaling, loop power and compliance voltage, differential wiring, M8 pinout, common-mode voltage, open-loop behavior, X2X mapping and IP67 sealing.
Alternative Names
X67AI1323 X67 AI1323 B&R X67AI1323 B&R X67 AI1323 BR X67AI1323 B&R X67 System X67AI1323 X67 System X67AI1323
Technical notes
X67AI1323 reads four differential current loops. Verify selected range, loop power, compliance voltage, input burden, polarity, grounding, M12 A-coded input wiring and project scaling before commissioning.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
Can B&R X67AI1323 power two-wire transmitters?
The module provides a documented sensor-supply budget, but verify loop topology, transmitter startup current, compliance voltage, total load and connector pinout.
Why does a 4–20 mA loop read low on B&R X67AI1323?
Check loop supply, input burden, cable resistance, polarity, transmitter scaling, leakage paths, connector resistance and the project range selection.
How should an open 4–20 mA loop be diagnosed on B&R X67AI1323?
Use the application under-range threshold together with field checks of loop power, transmitter output, cable continuity, connector pins and channel raw value.
Can B&R X67AI1323 read bipolar current signals?
It is specified for 0–20 mA or 4–20 mA process ranges; do not use it as a general bipolar current input.
What limits the speed of B&R X67AI1323 measurements?
The 400 µs conversion, input filter, X2X cycle, controller task and application filtering all contribute to total response time.
Can channels on B&R X67AI1323 share loop returns?
Do not assume so. Preserve the documented differential pinout and verify common-mode limits, grounding and transmitter isolation for every channel.
What should be recorded before replacing B&R X67AI1323?
Record range and scaling, alarm thresholds, loop power, connector labels, polarity, grounding and shielding, X2X position and current calibration checks.