Features:
- Interface Between the Universal AC Power Source and 3500 Rack Backplane
- Combines Capability of AC/DC Power Conversion with Redundant Power Support
- Operates in Conjunction with the M Series and Standard 3500 Monitors
The 3500/04 136719-01 128275-01F operates as the Universal AC Power Supply in a 3500 rack, providing reliable DC power to all modules within the system. It continuously converts incoming AC power (85-264 VAC, 47-63 Hz) to regulated 24 VDC and distributes this power through the rack backplane to support steady state operation of all monitors and modules. Seamless power transfer is standard with the 3500/04 136719-01 128275-01F, however using an optional Redundant Power Configuration will allow seamless switchover to a backup supply in the event of a primary power failure. The 3500/04 136719-01 128275-01F has made improvements in several areas over previous power supply designs in addition to incorporating universal input voltage capability within the 3500 rack..
The 3500/04 136719-01 128275-01F provides essential power functions common to the entire rack, and is a critical component of the monitoring path, directly affecting the proper, normal operation of the overall monitor system. One or two 3500/04 136719-01 128275-01F power supplies are required per rack depending on the desired redundancy level. The 3500/04 136719-01 128275-01F occupies only a single half-height slot in the rack and is always located in Slot 0 (far left position, the dedicated power supply slots).
For Dual Redundant Power applications, the 3500 System requires a second 3500/04 136719-01 128275-01F power supply module installed in the redundant slot. In addition to standard single supply operation, the redundant configuration also performs automatic switchover. The 3500 dual power configuration executes failover using the internal circuitry specified in the power supply options. Using this method, the redundant power system continually monitors the health of both supplies. If the system detects that the primary power supply is no longer providing stable output (outside configured voltage/ tolerance levels), it will automatically transfer the load to the secondary supply and place an event in the System Event List.
The 3500/04 136719-01 128275-01F Bently Nevada Universal AC Power Supply may still be available for purchase and support from Apter Power beyond End-Of-Life (EOL) by the manufacturer (OEM).
Bently Nevada 3500/04 136719-01 128275-01F Universal AC Power Supply Manuals,Datasheets, Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Bently Nevada 3500/04 136719-01 128275-01F Universal AC Power Supply
General
- Manufacturer GE / Bently Nevada
- Model 3500/04 136719-01 128275-01F
- Condition New Original ready stock
- Product Family 3500/04,136719-01,128275-01
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
- Rack Positioning: To maintain efficiency and safety, the IS Earthing Module requires a dedicated I/O position, which limits a standard 19-inch rack to 13 monitor positions.
- Wiring Separation: For optimal performance and safety compliance, installers must maintain a 50 mm (2 in) physical separation between safe and hazardous area field wiring.
- Cooling Efficiency: According to Newgen PLC, these plates are essential for maintaining proper airflow throughout the rack, preventing hotspots and ensuring the long-term reliability of active modules.
- Protection: It protects internal backplane components from dust and debris while maintaining a professional, uniform aesthetic.
- Software Requirement: Revision 2.3 or later of the 3500 Rack Configuration Software is mandatory to enable internal barrier support.
- 136719-01 Earthing I/O Module: This is a passive electrical safety component; it does not contain a microprocessor and therefore cannot be updated via firmware.
- 128275-01F Blank Plate: This is a mechanical cover made of metal alloy. It contains no electronic components and does not have firmware
- Explosion Protection: The 3500/04 internal barriers provide an intrinsically safe interface for transducer systems (like proximity probes or accelerometers) connected directly to the 3500 rack.
- IS Grounding: The 136719-01 Earthing I/O Module is a mandatory requirement for any rack containing internal barriers, as it provides the critical IS earth connection via the backplane.
- Hazardous Area Connectivity: It allows standard monitors (e.g., 3500/25, 3500/42, 3500/50) to interface with sensors located in hazardous zones without needing external barrier cabinets.