Features:
- Executes safety logic for emergency shutdown and process protection.
- -40°C to +70°C, 10g shock, ISA G3, 5-95% humidity.
- Ex ec IIC Gc, ATEX, and Class I Div 2/Zone 2 approvals.
The KJ2201X1-BA1 12P3162X242 SLS1508 is a SIS (Safety Instrumented System) Logic Solver module designed for the Emerson DeltaV scalable process control system. This module executes critical safety logic for emergency shutdown (ESD), fire and gas (F&G), and burner management systems (BMS) applications. The KJ2201X1-BA1 12P3162X242 SLS1508 operates on 24V LocalBus power at 1A and supports field power up to 4A, ensuring reliable power delivery for safety-critical functions.
The KJ2201X1-BA1 12P3162X242 SLS1508 is engineered for reliable operation in harsh industrial environments. It operates over an extreme temperature range of -40°C to +70°C and can withstand shock of 10g half-sine for 11ms. The KJ2201X1-BA1 12P3162X242 SLS1508 features vibration resistance of 1mm peak-to-peak from 2 to 13.2Hz and 0.7g from 13.2 to 150Hz. The KJ2201X1-BA1 12P3162X242 SLS1508 complies with ISA-S71.04-1985 Class G3 airborne contaminants and operates with 5-95% non-condensing relative humidity.
The KJ2201X1-BA1 12P3162X242 SLS1508 carries multiple hazardous area approvals including II 3G Ex ec IIC Gc, FM16ATEX0056U, and FM21UKEX0017U certifications. The KJ2201X1-BA1 12P3162X242 SLS1508 also holds CL.I Div.2 GP.A,B,C,D and CL.I Zone 2 AEx/Ex ec IIC Gc certifications, making it suitable for installation in potentially explosive atmospheres. The KJ2201X1-BA1 12P3162X242 SLS1508 requires field power to be removed before connecting or removing the device, and contains no user-serviceable parts.
The KJ2201X1-BA1 12P3162X242 SLS1508 EMERSON SIS Logic Solver may still be available for purchase and support from Apter Power beyond
End-Of-Life (EOL) by the manufacturer (OEM).
EMERSON KJ2201X1-BA1 12P3162X242 SLS1508 SIS Logic Solver Manuals,
Datasheets, Drivers, Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not
included with this equipment unless listed in the above stock item description. All prices are
shown in USD.
EMERSON KJ2201X1-BA1 12P3162X242 SLS1508 SIS Logic Solver Specs
General
- Manufacturer EMERSON
- Model KJ2201X1-BA1 12P3162X242 SLS1508
- Condition New Original ready stock
- Product Family
KJ2201X1-BA1 12P3162X202 SLS1508,KJ2201X1-BA1 12P3162X142 SLS1508
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not
included with this equipment unless listed in the above stock item description. All prices are
shown in USD.
- Refining & Petrochemical Processing: Monitors continuous chemical reactions and safely cuts off fuel or chemical feeds during hazardous process deviations.
- Oil & Gas (Upstream/Midstream): Integrated into offshore drilling platforms, Floating Production Storage and Offloading (FPSO) vessels, and cross-country transport pipelines.
- Power Plant Utilities: Manages critical trip loops for high-pressure boilers, gas turbine fuel supplies, and heavy industrial steam generators.
- Hazardous Manufacturing Enclosures: Implemented as the core safety barrier in volatile chemical blending zones and storage tank farms.
- Ex ec Zone 2 Protection: Certified to II 3G Ex ec IIC Gc and FM Class I, Division 2, enabling safe operation in hazardous atmospheres without sparking risks.
- ISA-S71.04 Class G3 Coating: The circuit board assembly features a conformal coating to protect internal components from harsh, corrosive chemical contaminants
- Shock & Vibration Isolation: Rated to withstand a 10g half-sinewave mechanical shock (11ms) and constant low-frequency industrial vibrations.
- Carrier Alignment: Slotted directly into an M-series 8-wide carrier base plate. To maintain appropriate structural layout and automated addressing, SLS1508 modules must occupy the odd slots (1, 3, 5, 7) on the carrier.
- Isolated 24 VDC Power Sourcing: Must be driven by an external, dedicated 24 VDC safety power supply. This safety supply must remain completely independent of the primary power grid driving the standard DeltaV DCS controllers to prevent common-cause electrical failures.
- Physical Wiring Isolation: Field cables route through a dedicated matching redundant terminal block (e.g., KJ2201X1-HA1). Ensure safety loop signals are segregated from low-voltage communication lines within standard wire duct paths.