Features:
- PK300 capacity: Provides 300 DST and four standalone batch units for mid-sized control applications.
- Native networking: Provides OPC UA and Modbus TCP server functions, with project-specific P01 client or scanner and integrated PROFINET options.
- Flexible deployment: Operates as a standalone controller or an integrated DeltaV system node.
KL2002X1-BB1 executes DeltaV control logic from process signals received through local I/O, CHARMs, wireless I/O and Ethernet devices.
Its PK300 capacity creates a practical middle point between compact packaged-equipment control and larger plant nodes, with module execution rates available from 25 ms to 60 seconds.
Built-in industrial Ethernet services and support for simplex or redundant node designs let KL2002X1-BB1 scale from an independent skid to a distributed DeltaV architecture.
For KL2002X1-BB1 DeltaV PK300 Controller sourcing, Apter Power can help confirm the Emerson capacity, carrier, power and software scope.
Emerson KL2002X1-BB1 DeltaV PK300 Controller Manuals,Datasheets,Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
- DST limit: 300 device signal tags.
- Ethernet devices: Up to 32 devices on port P01.
- PROFINET scale: Up to 100 devices with v15.FP1/FP2 or 250 with v15.FP3 and later.
- Standalone batching: Supports four standalone batch units.
- Modbus TCP: Native server service is included; P01 can run the client when EtherNet/IP Scanner is not selected.
- EtherNet/IP: P01 can run Scanner service instead of Modbus TCP Client, not at the same time.
- PROFINET: Controller service requires integrated DeltaV operation with the applicable version and license.
- OPC UA: Includes an OPC UA Server for real-time data access.
- Standalone operation: Runs packaged or remote equipment without a separate DeltaV controller tier.
- Integrated operation: Joins a wider DeltaV system as a controller node.
- I/O expansion: Supports local traditional I/O carriers plus electronic and wireless marshalling options.
- Node redundancy: A second adjacent controller can form a redundant node when the required hardware is installed.
- Packaged process skids: Combines standalone control, batching and industrial Ethernet in one controller platform.
- Remote process units: The environmental range and distributed I/O options support installation close to equipment.
- DeltaV expansion: Adds a 300-DST controller node to plant-wide DeltaV architectures.
- Mixed I/O projects: Coordinates traditional I/O, CHARMs, WirelessHART I/O and Ethernet devices within one control application.