Features:
- Drives 24 VDC solenoid coils with a 500 mA continuous safety output.
- Supervises the field loop with defined short-circuit, normal-load, and open-circuit thresholds.
- Combines inrush limiting, field-wiring disconnect, and common field-power shutoff.
The current ordering configuration is KL3302X1-BA1, the DeltaV SIS LS DO 24 VDC DTA CHARM.
It provides a monitored discrete output for safety solenoids in electronic-marshalling applications, including de-energize-to-trip service.
Before use, verify DTA terminal hardware, 3C keying, load resistance, line-fault settings, relay-terminal fuse protection, and project approval.
Availability is subject to Apter Power inventory and sourcing confirmation.
Verified resources for Emerson KL3302X1-BA1:
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
- Operates safety shutdown solenoids and final elements in DeltaV SIS electronic-marshalling cabinets.
- Supports de-energize-to-trip output strategies that remove field power through the common shutoff signal.
- Provides monitored 24 VDC actuation for emergency shutdown, burner management, and process-protection functions.
- Identifies a guaranteed short circuit when connected load resistance is below 10 Ω.
- Reports the guaranteed good-status region for loads from 56 Ω to 3.5 kΩ.
- Identifies a guaranteed open circuit when connected load resistance exceeds 20 kΩ.
- Delivers 500 mA continuously at 24 VDC for the connected solenoid load.
- Limits output inrush current to 580 mA to protect the field circuit.
- Performs the documented line-fault test with a 200 µs timing interval.
- Provides a 580 mA current-limiting circuit together with a field-wiring disconnect.
- Removes field power when the common shutoff signal is logic low for de-energize-to-trip operation.
- Requires external fuse protection when used with the LS CHARM relay output terminal block.