Features:
- Two module positions on one Field Control base
- Keyable cable interfaces for position identification
- Backplane path retained through the terminal assembly
IC670CHS003 combines mechanical support, module-to-module communication, and detachable user cabling in one DIN-rail-mounted assembly.
Because each module position has its own keyed connector, cable identity can be preserved during service without moving individual field conductors at the base.
Module retaining screws, connector seating, and the conductive rail bond are all part of the completed assembly and should be inspected after a replacement is fitted.
The General Electric IC670CHS003 I/O Terminal Block with Wire-to-Board Connectors may remain available for quotation and legacy-system support through Apter Power.
General Electric IC670CHS003 I/O Terminal Block with Wire-to-Board Connectors Manuals, Datasheets, Links
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
General Electric IC670CHS003 I/O Terminal Block with Wire-to-Board Connectors Specs
General
- ManufacturerGeneral Electric
- ModelIC670CHS003
- ConditionNew Original ready stock
- Product FamilyField Control Distributed I/O
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Cable Interface Details
- Connector count: One 20-pin male connector is provided for each module position.
- Mating part: AMP 178289-8 is the documented mating connector.
- Keying: Connector keying should be set before field cables are installed.
- Cable options: Use the approved Field Control cable or prepare contacts with the specified tooling.
DIN-Rail Installation
- Rail size: Install the base on a conductive 35 x 7.5 mm DIN rail.
- Ground path: The conductive rail forms part of the required chassis-ground arrangement.
- Base position: Seat the terminal block squarely before tightening its mounting hardware.
- Clearance: Allow room for cable bends, connector access, and installed module depth.
Service Restrictions
- Power removal: De-energize the station before installing or removing an I/O module.
- No hot swap: IC670CHS003 does not provide the alignment features required for hot insertion.
- Retaining screws: Release the module retaining screws before lifting the electronics assembly.
- Recheck: Inspect connector seating and keying before restoring system power.