Technical specifications for IC610MDL151

  • Manufacturer:
    General Electric
  • Part Number:
    IC610MDL151
  • Product Family:
    GE Intelligent Platforms
  • Product Type:
    Series One 8-Circuit 24 VDC Sink Output Module
  • Stock:
    1
  • Output points:
    8
  • Output type:
    24 VDC sink
  • Operating voltage:
    5 to 24 VDC
  • Maximum point current:
    0.5 A, temperature dependent
  • Maximum leakage current:
    0.1 mA at 40 VDC
  • Maximum inrush:
    3 A for 20 ms; 1 A for 100 ms
  • Switching response:
    100 ms OFF-to-ON; 100 ms ON-to-OFF
  • Internal fuses:
    Two 3 A fuses, one per four-point group
  • Native platform:
    GE Series One
  • Weight:
    0.26 lbs (0.12 kg)
  • Tariff Code:
    8537101190
  • Country of origin:
    USA
  • Place of shipment:
    Xiamen,Fujian,China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Sink Switching Load Planning Circuit Protection Rack Integration

Features:

  • Eight sink-output circuits switch user-supplied discrete loads from a common DC source.
  • Each point operates from 5 to 24 VDC and carries up to 0.5 A, subject to ambient derating.
  • Two internal 3 A fuses protect the two four-circuit output groups.
Sink switching places current flow from the connected load into the energized output terminal, so field polarity must follow the designated common arrangement.

Relay coils, motor starters, solenoid valves and indicator lamps are representative discrete loads when their steady-state and inrush demands remain within the circuit ratings.

Logic-side indication follows each commanded point, while the external DC source supplies the actual field load.

The General Electric IC610MDL151 Series One 8-Circuit 24 VDC Sink Output Module may still be available for purchase and support from Apter Power beyond End-Of-Life (EOL) by the manufacturer (OEM).
General Electric IC610MDL151 Sink Output Module Manuals,Datasheets,Link Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.

Current Path Details

  • Output Action: An energized point pulls current from the field load toward the module common.
  • Field Source: One external DC supply references all eight output circuits.
  • Voltage Window: Connected circuits operate from 5 to 24 VDC.
  • Point Limit: Each channel is rated up to 0.5 A within the temperature curve.

Device Demand Checks

  • Steady Load: Confirm each device remains below the continuous channel rating.
  • Startup Surge: Allow no more than 3 A for 20 ms or 1 A for 100 ms.
  • Minimum Current: A connected load should draw at least 1 mA when commanded.
  • Heat Derating: Reduce simultaneously loaded points as ambient temperature rises.

Group Safeguards

  • Fuse Layout: Two internal 3 A fuses divide protection between four-channel groups.
  • Leakage Level: OFF-state leakage is limited to 0.1 mA at 40 VDC.
  • Voltage Drop: The ON-state drop is specified at 0.8 V with a 0.5 A load.
  • Status View: Logic-side indication identifies the commanded condition of each circuit.

Series One Placement

  • Module Slot: IC610MDL151 occupies one compatible Series One I/O position.
  • Reference Order: Output addresses follow the module's physical rack location.
  • Power Budget: The rack load calculation must include both 9 VDC and 24 VDC requirements.
  • Service Match: Preserve terminal assignments and sink polarity when exchanging a field unit.
Description
General Electric IC610MDL151 adds eight sink-type DC output points to a Series One controller for operating discrete devices such as relay coils, solenoid valves, motor starters and indicator lamps.

When an output turns on, General Electric IC610MDL151 draws current from the connected load into its field terminal. All eight points reference one user-supplied DC source, so common polarity and return wiring must remain consistent across the module.

For panel design, General Electric IC610MDL151 separates the eight channels into two internally fused groups of four. The arrangement gives each half of the module group protection while preserving individual control at every output point.

A replacement General Electric IC610MDL151 should be checked against the actual load current, startup surge and cabinet temperature before service. The permitted point current is temperature dependent, and the field supply is not furnished by the module.
Alternative Names
IC610-MDL151 IC610 MDL151 IC 610 MDL 151 GE IC610MDL151 GE Fanuc IC610MDL151 Series One IC610MDL151 IC610MDL151 sink output IC610MDL15I
Technical notes
General Electric IC610MDL151 provides eight 5 to 24 VDC sink outputs in two internally fused groups. Confirm external DC polarity, load surge and ambient derating before energizing the module.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
How does General Electric IC610MDL151 switch a field device?
When a point is energized, General Electric IC610MDL151 sinks current from the user-powered load into the selected output terminal.
Which loads are suitable for IC610MDL151 in a Series One panel?
IC610MDL151 can control compatible relay coils, motor starters, solenoid valves and indicator lamps after their current and inrush are verified.
Why must IC610MDL151 use an external DC source?
The field devices receive power from a user-supplied source; IC610MDL151 provides the switching path rather than load power.
What should be checked before replacing General Electric IC610MDL151?
Match the Series One slot assignment, common polarity, 5 to 24 VDC field range and connected load demand before installing General Electric IC610MDL151.
Are temperature limits relevant when loading all eight IC610MDL151 outputs?
The allowable loading of IC610MDL151 depends on cabinet temperature, so the point-versus-temperature curve must be applied to the planned channel count.
How are the output circuits protected on IC610MDL151?
Two internal 3 A fuses protect IC610MDL151, with one fuse assigned to each group of four sink outputs.