Features:
- Eight sink-output circuits switch user-supplied discrete loads from a common DC source.
- Each point operates from 5 to 24 VDC and carries up to 0.5 A, subject to ambient derating.
- Two internal 3 A fuses protect the two four-circuit output groups.
Sink switching places current flow from the connected load into the energized output terminal, so field polarity must follow the designated common arrangement.
Relay coils, motor starters, solenoid valves and indicator lamps are representative discrete loads when their steady-state and inrush demands remain within the circuit ratings.
Logic-side indication follows each commanded point, while the external DC source supplies the actual field load.
The General Electric IC610MDL151 Series One 8-Circuit 24 VDC Sink Output Module may still be available for purchase and support from Apter Power beyond End-Of-Life (EOL) by the manufacturer (OEM).
General Electric IC610MDL151 Sink Output Module Manuals,Datasheets,Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Current Path Details
- Output Action: An energized point pulls current from the field load toward the module common.
- Field Source: One external DC supply references all eight output circuits.
- Voltage Window: Connected circuits operate from 5 to 24 VDC.
- Point Limit: Each channel is rated up to 0.5 A within the temperature curve.
Device Demand Checks
- Steady Load: Confirm each device remains below the continuous channel rating.
- Startup Surge: Allow no more than 3 A for 20 ms or 1 A for 100 ms.
- Minimum Current: A connected load should draw at least 1 mA when commanded.
- Heat Derating: Reduce simultaneously loaded points as ambient temperature rises.
Group Safeguards
- Fuse Layout: Two internal 3 A fuses divide protection between four-channel groups.
- Leakage Level: OFF-state leakage is limited to 0.1 mA at 40 VDC.
- Voltage Drop: The ON-state drop is specified at 0.8 V with a 0.5 A load.
- Status View: Logic-side indication identifies the commanded condition of each circuit.
Series One Placement
- Module Slot: IC610MDL151 occupies one compatible Series One I/O position.
- Reference Order: Output addresses follow the module's physical rack location.
- Power Budget: The rack load calculation must include both 9 VDC and 24 VDC requirements.
- Service Match: Preserve terminal assignments and sink polarity when exchanging a field unit.