Ask our team:
  • Phone: +86 181 0690 9650
  • E-Mail sales1@apterpower.com
  • Lifecycle status

    Discontinued / Obsolete by OEM
    Apter Power can help source this GE Fanuc View panel and review the stated configuration for a service enquiry.

IC754VSF12CTD-CB

/ 4.9
1001 reviews | Need a Specific Revision?
General Electric IC754VSF12CTD-CB is a 12-inch QuickPanel View touchscreen operator interface with the standard overlay for industrial machine visualization.
In Stock
Ships by Wednesday, October 28
Fast Shipping Available
Get a quick price for IC754VSF12CTD-CB
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for IC754VSF12CTD-CB

  • Manufacturer:
    General Electric
  • Part Number:
    IC754VSF12CTD-CB
  • Product Family:
    GE QuickPanel
  • Product Type:
    12-inch QuickPanel View HMI
  • Stock:
    1
  • Display:
    12-inch color TFT touchscreen
  • Display Resolution:
    800 x 600 pixels
  • Display Colors:
    65,536
  • DRAM:
    64 MB
  • Flash Memory:
    64 MB
  • Battery-backed SRAM:
    512 KB
  • Supply Input:
    24 VDC, 2 A, 48 W (nameplate)
  • Enclosure Size:
    301.1 x 226.8 x 60.1 mm
  • Bezel Size:
    336.8 x 262.6 x 9.7 mm
  • Nameplate Model:
    ES1222R
  • Overlay:
    Standard
  • LAN Ports:
    2 x 10/100 Mb Ethernet, auto-negotiating
  • Serial Ports:
    COM1 EIA232C/EIA485; COM2 EIA232C
  • USB Host Ports:
    2 x USB 1.1
  • CompactFlash Slot:
    1 x Type I/II, 3.3 V or 5 V
  • Operating Temperature:
    0 to 50 °C
  • Operating System:
    Microsoft Windows CE
  • Weight:
    2.36 kg
  • Tariff Code:
    Please confirm the destination before shipping
  • Country of origin:
    USA
  • Place of shipment:
    Xiamen,Fujian,China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Project Transfer Panel Installation Network Setup Product Applications

Features:

  • Standard-overlay View: GE's S configuration identifies the faceplate fitted to this 12-inch operator panel.
  • Machine Edition project: The touchscreen presents objects and screens defined by its deployed application.
  • Onboard interfaces: Ethernet, serial and removable-media facilities are documented for the QuickPanel View hardware.
IC754VSF12CTD-CB combines a standard-overlay touch front with a QuickPanel View computer behind the panel.

The installed application determines which screens and controls appear, while the hardware supplies the display and operator input surface.

GE documents network and removable-media setup separately from the physical catalog identity; the project and site configuration therefore remain distinct records.

Apter Power can help review the General Electric IC754VSF12CTD-CB 12-inch QuickPanel View HMI nameplate and available product records before quotation.
General Electric IC754VSF12CTD-CB 12-inch QuickPanel View HMI Manuals,Datasheets,Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
  • Project-copy utility: GE provides RestorePCCard for moving a Machine Edition project through external flash media.
  • Media choices: The manual lists CompactFlash and USB flash as project-transfer media.
  • Optional route: PCMCIA transfer uses the optional expansion interface described by GE.
  • Multiple devices: When more than one flash device is present, the utility opens a Select Media dialog.
  • Panel opening: GE provides a cutout drawing for the 12-inch QuickPanel View enclosure.
  • Insertion sequence: GE's illustrated mounting steps show the CF card, attached cables and power plug removed before the panel passes through the opening.
  • Mounting hardware: Ten brackets occupy housing openings distributed across the top, bottom and sides.
  • Bezel seal: The manual shows a gasket seated in the bezel channel before the mounting clamps are tightened.
  • Ethernet address: GE describes both DHCP and manually assigned IP settings in the Windows CE network configuration.
  • Device name: The configured network identity is stored separately from the Machine Edition screen project.
  • Link indicators: Ethernet link and activity LEDs offer distinct observations during connection checks.
  • Serial roles: COM1 supports EIA232C/EIA485 settings, while COM2 is documented for EIA232C.
  • Factory-floor visualization: Use the deployed View application to show machine or process information at the operator station.
  • Operator interaction: Present touch targets for the machine tasks defined by the installed HMI project.
  • Published information: Display project-published panel data through a standard browser when web access is configured for the installation.
  • Deployment choice: GE supports QuickPanel View use as a networked or standalone HMI where the application and installed links permit it.
Description
IC754VSF12CTD-CB is a GE Fanuc QuickPanel View touchscreen HMI with the standard overlay. Its display presents screens and touch objects defined by a Machine Edition application, keeping the hardware identity distinct from the project loaded onto it.

On IC754VSF12CTD-CB, touch interaction works with configured serial and Ethernet communications. Those links carry application data, so the panel needs its deployed project and site network settings to show the values and controls intended at the operator station.

The IC754VSF12CTD-CB rear nameplate gives the full catalog code and hardware model ES1222R. The two identifiers describe the physical unit; application loading and interface configuration are separate setup tasks.
Alternative Names
IC754VSF12CTD
Technical notes
When copying the Machine Edition project from IC754VSF12CTD-CB, GE warns that runtime file writes inside project folders can leave the copy incomplete. Pause those writes before using RestorePCCard, then let the flash-write activity finish before treating the saved files as a recovery copy. This protects the project record without assuming that a powered panel contains a usable backup.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
A project update card is inserted before IC754VSF12CTD-CB starts; will the panel always ask before installing it?
No. Wait for Answer is the default Project Transfer setting, but Always Restore mode installs a valid update without the usual confirmation. Check the selected mode before leaving update media in the panel at startup.
Touches on IC754VSF12CTD-CB land beside their on-screen targets; what is the first maintenance step?
Recalibrate the touch surface first. GE lists displaced targets as a calibration symptom and gives a Control Panel > Stylus > Calibration path. Retest the touch points after calibration before pursuing a separate hardware fault.
IC754VSF12CTD-CB responds slowly although touch positions are accurate; where should fault-finding begin?
GE lists configured serial or Ethernet errors and flash-storage problems among causes of slow touch response. Review those diagnostics first, then reassess response time after the communication or storage fault is corrected.
The IC754VSF12CTD-CB screen is dark; how can an operator check whether the backlight timer expired?
Touch the screen once: GE says a timer-expired backlight can reactivate that way. If the display stays dark, follow the manual’s separate power-connection and backlight diagnostic paths; a blank screen alone does not identify which fault is present.
Network settings on IC754VSF12CTD-CB disappear after a restart; must the Machine Edition project be redeployed?
Not for that symptom alone. GE's Backup utility saves Windows CE registry and desktop changes to Flash. Save the corrected settings with Backup, restart, and verify they persist before changing the visualization project.
The clock on IC754VSF12CTD-CB resets after power is removed; is the visualization project the first suspect?
No. GE identifies the internal Panasonic BR2032 as backup power for the real-time clock and SRAM when main DC power is absent. Investigate the battery condition before changing an otherwise working visualization project; use the manufacturer's battery-service instructions for any physical intervention.