Features:
- Creates a dedicated field landing point between XDSA, TCSA and the R2 controller hardware.
- Brings four FMVED serial channels to the PCM daughterboard in R2.
- Uses dedicated power and communication connectors to separate the two field-device functions.
DS200TBSAG1A occupies location eight of R2 and separates the pressure-sensor path from the FMVED communication routes.
P3 returns transducer pressure signals to TCSA, while P4 delivers the same 12 VDC source to the FMVED motor controllers.
The serial section reaches the PCM daughterboard without mixing its cabling with the pressure-transducer branch.
Apter Power offers sourcing coordination and system-fit assistance for the General Electric DS200TBSAG1A serial termination module.
General Electric DS200TBSAG1A Serial Communication Termination Module Manuals, Datasheets, Links
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Pressure Interface
- Field Source: Pressure wiring arrives from the externally mounted XDSA board.
- Sensor Excitation: The DLE devices receive their operating feed through the P3 branch.
- Return Path: Pressure signals travel back through P3 to TCSA.
- Core Link: TCSA receives the sensor path in the R core.
Serial Pairing
- Channels 1-2: P5 connects the first two FMVED links to the PCM daughterboard.
- Channels 3-4: P6 carries the remaining two communication links.
- Destination: Both channel pairs terminate at the PCM daughterboard on UCPB.
- Enable Control: JP1 through JP16 switch transmit and receive circuits into service.
Twelve-Volt Routes
- Source: TCSA supplies 12 VDC to the termination module.
- Sensor Branch: P3 feeds the DLE pressure transducers.
- Controller Branch: P4 powers the FMVED motor controllers.
- Separation: Power and serial-channel connectors remain functionally distinct.
Documented Uses
- DLE Service: The board is used with DLE pressure-transducer installations.
- External Board: XDSA provides the field-side pressure wiring.
- Motor Control: FMVED motor-controller links terminate on TBSA.
- Panel Position: The assembly sits in location eight of the R2 core.