Ask our team:
  • Phone: +86 181 0690 9650
  • E-Mail info@apterpower.com
  • Lifecycle status

    Discontinued / Obsolete by OEM
    For DS200TBQGG1A, Apter Power supports quotations, official documentation access and TBQG signal-path matching.

DS200TBQGG1A

/ 4.9
1001 reviews | Need a Specific Revision?
Within the SPEEDTRONIC Mark V gas-turbine control, General Electric DS200TBQGG1A is an analog I/O termination board for optional current-output and current-or-voltage input paths.
In Stock
Ships by Tuesday, September 29
Fast Shipping Available
Get a quick price for DS200TBQGG1A
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for DS200TBQGG1A

  • Manufacturer:
    General Electric
  • Part Number:
    DS200TBQGG1A
  • Product Family:
    SPEEDTRONIC Mark V
  • Product Type:
    Mark V Analog I/O Termination Board
  • Stock:
    1
  • Board Designation:
    TBQG
  • Core Position:
    S core termination interface
  • Current Outputs:
    Four 4-20 mA channels, terminals 25-32
  • Analog Inputs:
    Four 4-20 mA or +/-10 VDC channels, terminals 33-44
  • Configuration Scope:
    Optional GHD feature
  • Tariff Code:
    8537101190
  • Country of origin:
    USA
  • Place of shipment:
    Xiamen,Fujian,China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Output Allocation Analog Receive Feature Boundary GHD Deployment

Features:

  • Adds four analog output terminations to the optional Mark V signal set.
  • Accepts four channels configurable for current or bipolar voltage input.
  • Uses separate terminal ranges for outgoing and incoming analog traffic.
DS200TBQGG1A divides its available terminals into an output block at 25-32 and an input block at 33-44.

The four input positions accommodate either 4-20 mA current or +/-10 VDC signals, depending on the configured measurement path.

This TBQG function is an optional GHD feature rather than a universal Mark V termination set.

Apter Power coordinates sourcing and documented signal-path support for the General Electric DS200TBQGG1A termination board.
General Electric DS200TBQGG1A Mark V Analog I/O Termination Board Manuals, Datasheets, Links Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.

Outgoing Channels

  • Quantity: Four analog current-output channels are provided.
  • Signal Form: Each outgoing path is designated for 4-20 mA.
  • Terminal Block: The four outputs occupy positions 25 through 32.

Input Choices

  • Input Bank: Four measurement paths occupy the TBQG receive side.
  • Current Mode: Select the current-input configuration for a 4-to-20 mA transmitter.
  • Voltage Mode: The alternative input form is +/-10 VDC.
  • Terminal Block: Incoming channels use positions 33 through 44.

Configuration Scope

  • Option Status: TBQG is identified as an optional Mark V feature.
  • PROM Set: The documented allocation applies to the GHD PROM set.
  • Signal Split: Outgoing and incoming circuits occupy separate terminal blocks.

Documented Context

  • System: The signal allocation belongs to SPEEDTRONIC Mark V.
  • Control Class: The feature is associated with gas-heavy-duty control configuration.
  • Core Path: The documented TBQG terminations are tied to the S-core option.
Description
Within the SPEEDTRONIC Mark V control architecture, General Electric DS200TBQGG1A is a TBQG analog I/O termination board. Its documented role is to provide an optional set of analog terminations associated with the S-core signal path.

On its output side, General Electric DS200TBQGG1A provides four 4-20 mA channels across terminal positions 25 through 32. These positions keep outgoing current signals grouped separately from the board's analog inputs.

For incoming measurements, General Electric DS200TBQGG1A assigns four channels to terminals 33 through 44, with each path supporting 4-20 mA current or +/-10 VDC voltage. The TBQG allocation is identified as an optional GHD feature associated with the S-core signal path.
Alternative Names
GE DS200TBQGG1A DS200 TBQG G1A TBQG G1A Analog I/O Board DS200TBQG-G1A Mark V DS200TBQGG1A General Electric DS200TBQG G1A DS 200 TBQG G1A DS2O0TBQGG1A
Technical notes
General Electric DS200TBQGG1A provides the optional Mark V TBQG termination set for four current outputs and four current-or-voltage inputs.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
How should a panel drawing be checked before assigning General Electric DS200TBQGG1A?
Confirm that General Electric DS200TBQGG1A is listed for the optional GHD signal set and that the unit-specific I/O schedule assigns the expected S-core TBQG positions.
Why would a voltage transmitter not fit an output position on General Electric DS200TBQGG1A?
General Electric DS200TBQGG1A reserves terminals 25-32 for 4-20 mA outputs; the current-or-voltage input paths are instead located at terminals 33-44.
Can General Electric DS200TBQGG1A accept both milliamp and bipolar voltage inputs?
Yes. The four input channels on General Electric DS200TBQGG1A are documented for 4-20 mA or +/-10 VDC, subject to the installed configuration.
Which terminal range helps isolate an input-side fault on General Electric DS200TBQGG1A?
Troubleshooting General Electric DS200TBQGG1A input wiring should focus on positions 33 through 44, leaving the output block at 25-32 out of that path.
What is the practical limit when considering General Electric DS200TBQGG1A for another Mark V panel?
General Electric DS200TBQGG1A is tied to an optional GHD allocation; do not assume the same TBQG terminal set is present without checking the target panel's I/O assignment.