Features:
- 0.5 m exact cable length
- 50-core flat I/O-bus construction
- Rear XD.1/XD.2 connection between H41q/H51q I/O subracks
Bus connection: The cable extends the H41q/H51q I/O bus between adjacent subracks through the rear bus connectors.
Length control: The 0.5 m suffix identifies the inter-subrack cable, while the complete installed I/O bus must remain within the HIMA 12 m total-length limit.
Physical handling: Correct connector orientation, strain relief and routing are necessary because the flat cable forms part of the shared I/O-bus path.
Apter Power supports HIMA BV7032-0.5 I/O Bus Connecting Cable documentation, quotations, procurement and bus-topology guidance.
HIMA BV7032-0.5 I/O Bus Connecting Cable Manuals,Datasheets,Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
- The cable links individual H41q/H51q I/O subracks.
- Rear connector XD.1 or XD.2 provides the I/O-bus connection point.
- Each inter-subrack link for this exact code is 0.5 m.
- All installed I/O-bus segments contribute to the 12 m total limit.
- BV7032 uses a 50-core flat-cable construction.
- The flat form should remain untwisted and free from sharp folds.
- Connector orientation must match the rear subrack bus interface.
- Cable routing should avoid strain at XD.1 and XD.2.
- Do not exceed 0.5 m between the linked subracks for this cable selection.
- Keep the complete H41q/H51q I/O bus at or below 12 m.
- Verify source and destination subracks before disconnecting an existing link.
- Inspect the shared bus path if several downstream subracks lose communication together.
- Adjacent H41q I/O-subrack bus connections.
- Adjacent H51q I/O-subrack bus connections.
- Legacy safety-system rack expansion within the documented bus-length limits.
- Maintenance of installed systems whose drawings specify BV7032-0.5.