HIMA F6217 is an eight-channel SIL 3 analog input module for current and voltage signals with safety isolation and on-board diagnostics.
In Stock
Ships by Saturday, November 14
Fast Shipping Available
Get a quick price for F6217
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for F6217

  • Manufacturer:
    HIMA
  • Part Number:
    F6217
  • Product Family:
    HIMA HIQuad H41q/H51q
  • Product Type:
    8-Channel Safety-Related Analog Input Module
  • Stock:
    1
  • Analog input channels:
    8
  • Current ranges:
    0 to 20 mA and 4 to 20 mA
  • Voltage ranges:
    0 to 5 V and 0 to 10 V
  • Safety capability:
    AK 6 / SIL 3
  • Conversion resolution:
    12 bit
  • Input voltage measurement span:
    0 to 5.5 V
  • Maximum input voltage:
    7.5 V
  • Input current measurement span:
    0 to 22 mA
  • Maximum input current:
    30 mA
  • Specified current shunt:
    250 Ω, 0.05%, 0.25 W
  • Shunt temperature coefficient:
    Below 10 ppm/K
  • Shunt part number:
    00 0710251
  • Measurement update:
    50 ms
  • Safety time:
    Below 450 ms
  • Input resistance:
    100 kohm
  • Input-filter time constant:
    Approximately 10 ms
  • Basic error:
    0.1% at 25 degrees C
  • Operating error:
    0.3% from 0 to 60 degrees C
  • Safety-related error limit:
    1%
  • Electric strength:
    200 V to ground
  • Space requirement:
    4 SU
  • Backplane supply:
    5 VDC at 80 mA
  • Field supply load:
    24 VDC at 50 mA
  • Dimensions:
    2.1 x 19.1 x 12.9 cm
  • Weight:
    0.14 kg
  • Tariff Code:
    8538900000
  • Country of origin:
    Germany
  • Place of shipment:
    Xiamen, Fujian, China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Signal Preservation Safety Handling Measurement Test Application
  • Eight current or voltage measurement channels
  • Redundant on-board processing and diagnostic tests
  • Safety-isolated analog acquisition for HIQuad systems

F6217 concentrates conversion and diagnostic checking within the module, reducing dependence on external conversion hardware while maintaining a defined safety response to measurement faults.

Its practical replacement boundary includes every shunt, shield and software scale; restoring only the card leaves the measurement chain incomplete and can produce plausible but unsafe values.

Commissioning should apply controlled signals at several points across every configured range and verify engineering units, alarm limits, diagnostics and the safety reaction to an invalid measurement.

Availability, condition, price, and shipping time for F6217 are confirmed during quotation.

HIMA F6217 8-Channel Safety-Related Analog Input Module Manuals, Product Family, Links

Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.

  • Record every channel range and engineering-unit scale
  • Keep precision shunts with their assigned current channels
  • Preserve shield and analog-reference connections from the project drawing
  • Map each channel fault bit to the validated process reaction
  • Review alarm and trip thresholds before live testing
  • Confirm redundant processor diagnostics return to a healthy state
  • Inject controlled values across every configured range
  • Compare field input, raw value and displayed engineering units
  • Verify alarms, interlocks and safe-state actions at defined points
  • Four-to-twenty milliamp transmitter acquisition in emergency shutdown systems
  • Voltage-signal monitoring in high-integrity pressure protection systems
  • Safety-related analog process measurement in fire and gas systems
Description
F6217 acquires eight safety-related analog channels for current or voltage signals. A redundant processor system performs conversion and module diagnostics directly on the board while safety isolation separates the analog circuitry from ground.

The module provides twelve-bit conversion, fixed update and safety timing, input filtering and defined accuracy limits. Current measurement uses the specified precision shunt, while screened cable arrangements support voltage and transmitter connections.

A replacement must reproduce the signal range, shunt or cable-plug arrangement, shielding, controller scaling and channel-fault reaction. Controlled signal injection should verify each measurement path from field terminals to safety logic.
Alternative Names
HIMA F6217 HIMA F 6217 HIMA HIQuad F6217 F 6217 F6217 SIL 3 Analog Input
Technical notes
HIMA F6217 replacement requires matched revision, channel ranges, precision shunts, shielded cable plugs, scaling and fault-bit logic; an incorrect current/voltage arrangement can invalidate safety measurements.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
Can current and voltage signals be mixed on HIMA F6217?
F6217 supports both signal types, but every channel must use the correct cable-plug and precision-shunt arrangement, controller scaling and field wiring for its selected range.
What should be backed up before replacing HIMA F6217?
Save the controller project and record each channel range, engineering-unit scaling, alarm limits, channel-fault reaction, shunt installation, cable plug and shield termination.
Why does HIMA F6217 show an offset after replacement?
Check the precision shunt, zero reference, shield grounding, cable resistance, signal-source calibration and configured scaling before changing application logic.
How should shielding be restored on HIMA F6217?
Use the screened cable and earth-bar connection shown by HIMA, keeping the project grounding method unchanged and avoiding additional shield connections that create ground loops.
What must the safety program do with an HIMA F6217 channel fault?
The channel fault bit must trigger the project-defined safety reaction. Verify that the restored program evaluates the bit and drives the process to its validated state.
Can HIMA F6217 be accepted using only a single calibration point?
No. Inject controlled values across the operating range on every channel and compare raw conversion, engineering units, diagnostics and alarm behavior.
Can HIMA F6217 be replaced by F6215 or F6221?