Features:
- Accepts four analog voltage input channels.
- Allows independent range selection for every channel.
- Provides 12-bit conversion and per-channel digital filtering.
HE800ADC110 combines four voltage inputs in the metal SmartStack form for applications that need several analog signals in one position.
Separate ranges and filter values let stable and noisy sensors coexist without forcing a common setup across all four channels.
Before energizing the module, match each terminal to its Cscape channel assignment and keep low-level signal cable separated from higher-current wiring.
The Horner HE800ADC110 Voltage Input Module may still be available for purchase and support from Apter Power beyond End-Of-Life (EOL) by the manufacturer (OEM).
Horner HE800ADC110 Voltage Input Module Manuals, Datasheets, Links
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
HE800ADC110 Voltage I/O
- Input capacity: Four analog voltage channels provide four PLC input points.
- Voltage spans: Choices include ±10.23 VDC, ±5.11 VDC, 0–10.23 VDC and 0–5.11 VDC.
- Measurement depth: A 12-bit successive-approximation converter processes the four signals.
- Source loading: Nominal impedance is 10 MΩ below 12 VDC and 6 MΩ above 12 VDC.
- Refresh behavior: Conversion timing is governed by the PLC scan.
HE800ADC110 I/O Mapping
- Status view: Cscape displays the operating state of the installed I/O.
- Register location: The I/O Map identifies assigned registers and the module position in the point map.
- Automatic assignment: Model number and SmartStack location determine the map, so users do not edit it.
- Channel ranges: A different supported voltage range may be selected for each input.
- Response control: Filter constants from 0 through 7 adjust digital filtering by channel.
HE800ADC110 Signal Wiring
- Terminal pattern: Each voltage input uses a positive connection, a common and a shield point.
- Field connector: The removable spring-clamp terminal block supports serviceable wiring.
- Signal cable: Shielded twisted-pair conductors are specified for best analog performance.
- Shield treatment: Shields may terminate at the module, or at the panel ground block in severe applications.
- Input safeguard: The published maximum overvoltage is 350 VDC.
HE800ADC110 PLC Match
- Hardware format: The HE800 ordering code identifies the metal-case SmartStack module.
- Plastic alternative: HE-ADC110 denotes the related plastic-case configuration.
- Document coverage: Equivalent IC300-prefixed products are included in the official datasheet.
- Setup reference: Controller-specific SmartStack procedures come from the hardware manual for that controller.
- Supply requirement: The analog inputs need no separate external power source.