Features:
- Provides four differential current inputs.
- Supports ±20 mA, 0–20 mA and 4–20 mA ranges.
- Delivers 16-bit conversion with selectable 50/60 Hz rejection.
Horner HE800ADC140 is the metal-case four-channel 16-bit SmartStack current input ordering configuration.
The module accepts common industrial current signals for higher-resolution monitoring in compatible controller applications.
Range selection, conversion timing, common-mode voltage and differential field wiring must be checked during system integration.
The Horner HE800ADC140 Current Input Module may still be available for purchase and support from Apter Power beyond End-Of-Life (EOL) by the manufacturer (OEM).
Horner HE800ADC140 Current Input Module Manuals, Datasheets, Links
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
HE800ADC140 16-Bit I/O
- Input structure: Four differential current channels are provided in one SmartStack module.
- Range choices: Supported selections are ±20 mA, 0–20 mA and 4–20 mA.
- Resolution: Current data is represented with 16-bit conversion.
- Conversion cycle: All four channels complete conversion in 313 ms.
- Input resistance: The published impedance is 5 Ω.
HE800ADC140 Noise Filter
- Cscape monitoring: The software provides access to module status during setup.
- Independent selection: Any supported current range can be chosen separately for each channel.
- Digital filter: The Filter Constant changes the response applied to the measured signal.
- Mains rejection: A 50 Hz or 60 Hz setting is available for line-frequency noise rejection.
- I/O placement: Register assignments follow the model number and SmartStack location rather than manual editing.
HE800ADC140 Input Safety
- Common-mode boundary: Differential inputs must remain within the specified ±12 VDC range.
- Out-of-range effect: Exceeding that boundary produces incorrect readings on the affected channel.
- Reference connection: Leaving one side of a differential input unconnected results in an effective zero reading.
- Reversed pair: Swapping differential polarity reverses the sign of the PLC data.
- Current ceiling: The maximum overcurrent rating is 100 mA.
HE800ADC140 Diff Wiring
- Channel conductors: Each loop uses positive, negative and shield terminals.
- Common reference: One side of every input may be tied to the OCS supply common to hold the required common-mode range.
- Cable pairing: Twisted pairs are required, with shielding preferred for analog signal quality.
- Connector hardware: The field block is removable and uses spring-clamp terminals.
- Module supply: Steady-state consumption is 0.62 W at 24 VDC, with no external input supply required.