Ask our team:
  • Phone: +86 181 0690 9650
  • E-Mail sales1@apterpower.com
  • Lifecycle status

    Discontinued / Obsolete by OEM
    Apter Power supports HE800DIM410 sourcing, input documentation and SmartStack system matching.

HE800DIM410

/ 4.9
1001 reviews | Need a Specific Revision?
Horner HE800DIM410 is a 32-channel SmartStack metal input module for bringing positive- or negative-logic 12/24 VDC field states into compatible controllers.
In Stock
Ships by Wednesday, October 28
Fast Shipping Available
Get a quick price for HE800DIM410
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for HE800DIM410

  • Manufacturer:
    HORNER
  • Part Number:
    HE800DIM410
  • Product Family:
    HORNER
  • Product Type:
    32-Channel 12/24 VDC Input Module
  • Stock:
    1
  • Inputs:
    32
  • Input Voltage:
    12–24 VDC
  • Input Logic:
    Positive or Negative
  • Isolated Commons:
    6
  • Isolation:
    500 VDC
  • Input Response:
    1 ms ON and OFF
  • Tariff Code:
    8537101190
  • Country of origin:
    USA
  • Place of shipment:
    Xiamen,Fujian,China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals DC Input Bank Common Isolation Signal Response I/O Mapping

Features:

  • Collects thirty-two discrete 12/24 VDC field states.
  • Works with positive- or negative-logic circuits.
  • Separates the input bank into six isolated common groups.
Horner HE800DIM410 is the thirty-two-point metal SmartStack ordering configuration; the related DIM310 version provides sixteen inputs.

Its high point count consolidates switches, contacts and DC sensor states into one stack position without adding output circuitry.

Confirm field polarity, six-group terminal allocation and module position before matching an existing I/O map.

The Horner HE800DIM410 32-Channel DC Input Module may still be available for purchase and support from Apter Power beyond End-Of-Life (EOL) by the manufacturer (OEM).
Horner HE800DIM410 32-Channel 12/24 VDC Input Module Manuals, Datasheets, Links Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.

HE800DIM410 Discrete DC Input Capacity

  • Point Count: Thirty-two discrete inputs are provided.
  • Field Range: Each point is intended for 12–24 VDC signals.
  • Peak Limit: The listed maximum peak input is 35 VDC.
  • Input Impedance: Each channel is specified at 10 kΩ.

HE800DIM410 Six-Group Electrical Isolation

  • Common Count: Six commons divide the thirty-two inputs.
  • Group Separation: Commons are isolated from one another.
  • Channel Barrier: Common-to-channel isolation is rated 500 VDC.
  • Terminal Style: Field wiring uses removable spring-clamp terminals.

HE800DIM410 Input Thresholds and Timing

  • ON Threshold: A channel turns on at 9 VDC minimum.
  • OFF Threshold: A channel is off at 3 VDC maximum.
  • Minimum Current: The stated ON current is 1 mA.
  • Transition Time: Both switching directions are specified at 1 ms.

HE800DIM410 Register Assignment Details

  • Register Basis: The I/O map follows the module model and stack location.
  • User Editing: The mapped register layout is not edited by the user.
  • Lower Bank: Inputs 1–16 occupy the first three common groups.
  • Upper Bank: Inputs 17–32 use common groups four through six.
Description
Horner HE800DIM410 expands a compatible metal SmartStack controller with thirty-two discrete DC input points. The bidirectional input circuitry accepts positive- or negative-logic wiring, so one module can accommodate the polarity convention already used by switches and sensors in an existing panel.

The thirty-two inputs on Horner HE800DIM410 are divided across six isolated commons. This grouping gives installers defined field-circuit sections while the 500 VDC common-to-common and common-to-channel isolation helps separate those sections electrically.

A signal is recognized as ON from 9 VDC and OFF at 3 VDC or below, with 1 ms response in either direction. Horner HE800DIM410 has no user-defined operating parameters; its register assignment is established by the module model and physical SmartStack position.
Alternative Names
HE800-DIM410 HE 800 DIM 410 HE800 DIM410 HEDIM410 HE-DIM410 Horner HE800DIM410 SmartStack DIM410 HE800DIM410 Input Module
Technical notes
Horner HE800DIM410 provides thirty-two bidirectional 12/24 VDC inputs in six isolated common groups. Its specified OFF-to-ON and ON-to-OFF response is 1 ms.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
Can Horner HE800DIM410 accept both positive- and negative-logic field signals?
Horner HE800DIM410 uses bidirectional 12/24 VDC inputs, allowing positive- or negative-logic operation when the field supply and commons are wired for the selected logic.
Why might one section of Horner HE800DIM410 inputs stop responding while others still work?
Horner HE800DIM410 divides its thirty-two points among six isolated commons, so a missing field supply or open common can affect only the channels assigned to that group.
What voltage levels should be checked when Horner HE800DIM410 shows an uncertain input state?
Horner HE800DIM410 specifies ON at 9 VDC minimum and OFF at 3 VDC maximum; signals between those levels should be corrected at the source or wiring.
Does Horner HE800DIM410 require per-channel setup in Cscape?
Horner HE800DIM410 has no user-defined module parameters; Cscape identifies its I/O map from the model and physical position in the SmartStack.
How quickly can Horner HE800DIM410 report a changing discrete signal?
Horner HE800DIM410 specifies 1 ms from OFF to ON and 1 ms from ON to OFF, while total controller reaction also depends on the PLC scan.
What should be verified before replacing a lower-density module with Horner HE800DIM410?
Before using Horner HE800DIM410, verify the need for thirty-two inputs, six common groups, 12/24 VDC logic, terminal assignments and the resulting I/O-map position.

Product Browsing History