Features:
- Commands four independent industrial current loops.
- Uses 14-bit conversion for fine actuator adjustment.
- Supports a defined or retained command during controller stop.
Horner HE800DAC106 denotes the metal-case DAC106 ordering configuration, while HE-DAC106 identifies the related plastic-case version.
The module serves controller applications that position valves, indicators or other compatible devices through four sourcing 0–20 mA circuits updated with the PLC scan.
Replacement matching should confirm that the receivers require sourcing current, the complete circuit stays within the available drive area and the selected stop response is safe for the equipment.
The Horner HE800DAC106 Current Output Module may still be available for purchase and support from Apter Power beyond End-Of-Life (EOL) by the manufacturer (OEM).
Horner HE800DAC106 Current Output Module Manuals, Datasheets, Links
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
HE800DAC106 Loop Outputs
- Channel count: Four sourcing outputs independently drive industrial current loops.
- Output span: The operating range extends from zero to 20.47 mA including overrange.
- Terminal pairs: Each channel has a positive output, common and shield connection.
- Controller update: Output commands are refreshed in step with the PLC scan.
HE800DAC106 Load Limits
- Loop resistance: The documented maximum load is 500 ohms.
- Compliance: Available output compliance is 10 VDC.
- Peak voltage: The maximum specified output voltage is 10 VDC.
- Output protection: The output circuitry uses 15 V, 300 W transient suppressors.
HE800DAC106 Stop Defaults
- Factory behavior: Outputs default to zero when the controller enters idle or stop mode.
- Assigned value: Module Setup can apply a specified fallback value to each output.
- Hold option: An output may be configured to retain its last value.
- Application review: A nonzero or held fallback must be checked against the safe state of connected equipment.
HE800DAC106 Current Scaling
- Conversion factor: The 0–20 mA range uses 0.000625 mA per program count.
- Full command: A value of 32000 represents 20.00 mA.
- Overrange point: The 20.47 mA output corresponds to a data value of 32752.
- Resolution: Fourteen-bit conversion supports fine current adjustments across the loop range.