Features:
- Accepts two thermocouple or millivolt channels.
- Supports seven thermocouple families and three bipolar mV ranges.
- Provides automatic internal or external cold-junction compensation.
Horner HE800THM000 is the two-channel metal SmartStack temperature-input configuration; the THM100 version expands the same measurement design to four channels.
Its selectable sensor and millivolt modes make it suitable for paired temperature points or low-level analog signals within one controller stack.
Choose the exact sensor type, unit format, filtering and noise-rejection frequency before using the returned analog values.
The Horner HE800THM000 Thermocouple Input Module may still be available for purchase and support from Apter Power beyond End-Of-Life (EOL) by the manufacturer (OEM).
Horner HE800THM000 2-Channel Thermocouple/Millivolt Input Module Manuals, Datasheets, Links
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
HE800THM000 Compatible Thermocouple Sensors
- Base-Metal Types: J, K, T and E are selectable.
- High-Temperature Types: C, R and S are also supported.
- Channel Count: Two sensors can be connected.
- Input Points: The module consumes two analog input registers.
HE800THM000 Cold-Junction Compensation Method
- Internal Method: Built-in junction compensation is supported.
- External Method: The module specification also provides an external compensation option.
- Selection: Compensation mode is selected automatically.
- Thermocouple Use: Junction compensation applies when a temperature-sensor type is configured.
HE800THM000 Low-Level Voltage Measurement Modes
- Narrow Range: ±25 mV maps to the full signed register span.
- Mid Range: ±50 mV is independently selectable.
- Wide Range: ±100 mV accommodates the largest listed signal.
- Accuracy: Millivolt measurement is specified at 0.1% full scale.
HE800THM000 Input Filtering and Rejection
- Filter Constant: Digital smoothing is adjustable in Module Setup.
- Reject Rate: Mains-noise rejection can be set to 50 or 60 Hz.
- Conversion: The integrating converter processes sixteen channels per second.
- Scan Relationship: PLC update timing follows the controller scan rate.