Features:
- Terminates sixteen controlled 4–20 mA loops for a Series 8 analog output module.
- Provides open-wire supervision and configurable output handling during fault conditions.
- Uses the coated, non-redundant six-inch IOTA construction identified by the full part number.
The ordering configuration is a coated termination assembly and does not include the 8C-PAOHA1 electronics.
It routes regulated analog commands from the C300 I/O subsystem to sixteen field-control loops.
Channel load, loop power and safe-state requirements should be recorded before moving wires from the existing IOTA.
Apter Power can review sourcing, documentation and system matching for 8C-TAOXA1 51307135-175.
Verified resources for Honeywell 8C-TAOXA1 51307135-175:
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
- Process units use the outputs to position control valves and variable actuators from Experion control strategies.
- Package systems can send isolated current commands to drives or converters that accept standard analog references.
- Maintenance cabinets use open-wire indication to identify a disconnected loop before loss of regulation causes a process upset.
- Sixteen independent current commands are controlled through the paired analog output electronics.
- Open-wire supervision identifies a field circuit that cannot maintain the commanded loop.
- Fault behavior can retain the last value or move the channel to a configured safe state.
- The direct 2.9 to 21.1 mA range gives the system margin for underrange and overrange diagnostics.
- Loop loading must remain inside the 50 to 800 ohm window for proper compliance.
- Coated construction supports use in the documented industrial cabinet environment.
- The termination assembly is designed for the Series 8 8C-PAOHA1 high-level analog output module.
- Its six-inch non-redundant format must match the existing carrier and cabinet layout.
- Control-system configuration must assign the correct channel type and safe-state behavior to all connected loops.