Features:
- Terminates sixteen high-level analog or smart-transmitter input circuits.
- Uses uncoated Size B construction with compression-terminal field connections.
- Routes each input channel to the matching HPM processor through the assigned cable path.
The present ordering configuration is the standard MU input FTA for sixteen channels. It is a non-CE assembly without conformal coating and draws 320 mA from the 24 V DC supply.
Process transmitter signals enter at the compression terminals and are delivered to the input processor for conversion and control-system use. This separation keeps routine field wiring accessible in the termination area.
Prior to replacement, compare the transmitter schedule, grounding, shield treatment, system cable and IOP mapping. Environmental suitability must be checked because the circuit assembly is uncoated.
Configuration and availability are reviewed against the connected input processor and cabinet conditions.
Verified resources for Honeywell MU-TAIH12 51304337-100:
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
- Terminates process transmitters that deliver supported high-level DC measurement signals.
- Provides the field interface for smart-transmitter channels in HPM process-control cabinets.
- Supports rewiring and maintenance projects that preserve the standard MU input architecture.
- Works with the corresponding high-level analog input processor through the designated Honeywell cable.
- Channel identities must remain consistent between the terminal schedule, IOP map and control database.
- Supported transmitter wiring must follow the grounding and shield arrangement defined for the cabinet.
- Sixteen process inputs are presented individually for conversion and status handling by the IOP.
- Post-replacement loop checks should compare each transmitter signal with the correct control-system point.
- Unexpected common drift should trigger inspection of shared grounding, shields and cable seating.
- The MU execution is supplied without conformal coating and is documented as non-CE hardware.
- Enclosure cleanliness and humidity control must be suitable for an uncoated circuit assembly.
- A mechanically similar coated variant should not be substituted without reviewing environmental qualification.