Features:
- One 4-20 mA analog input channel with HART in the supported source modes.
- SIL 2 three-way galvanic isolation between field, power, and control interfaces.
- Transparent field open-wire status and reverse-polarity protection.
Two-wire and three-wire source devices connect through the assigned A, B, and C terminals, while current-sink arrangements use the supported two-wire or four-wire paths.
The barrier works with the CC-UGIA01 universal signal conditioning assembly, whose three-tier terminal blocks provide the field connections for the isolated channel.
Mechanical keying, screwless backplane mounting, and a -40 to +70 deg C operating range support dense safety marshalling cabinets and hazardous-location loop designs.
Apter Power can assist with safety-loop matching, official documentation, and pricing for the Honeywell FC-UGAI01 Analog Input Barrier Module for Safety.
Honeywell FC-UGAI01 Analog Input Barrier Module for Safety Manuals, Datasheets, Links
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Honeywell FC-UGAI01 Analog Input Barrier Module for Safety Specs
General
- ManufacturerHoneywell
- ModelFC-UGAI01
- ConditionNew Original ready stock
- Product FamilyHoneywell Safety Systems
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
FC-UGAI01 Analog Input Configurations
- Two-wire source: Supports 4-20 mA with HART on the documented A and B terminals.
- Three-wire source: Supports 4-20 mA with HART using the documented A, B, and C terminals.
- Current sink: Supports two-wire or four-wire 4-20 mA current-sink service.
- Field terminals: Connections are provided through the three-tier terminal blocks on CC-UGIA01.
FC-UGAI01 Barrier Protection Functions
- Isolation: Three-way galvanic isolation separates the relevant safe and hazardous-location interfaces.
- Open wire: Field-side open-wire conditions are passed transparently for diagnostics.
- Polarity: The module includes reverse-polarity protection.
- Short circuit: The documented field short-circuit current is 23.5 mA.
FC-UGAI01 Mounting and Environment
- Mounting: The keyed module uses screwless backplane mounting with a base plate and housing.
- Temperature: The operating range is -40 to +70 deg C.
- Humidity: Permissible operating humidity is 5 to 95% non-condensing.
- Safety review: Confirm hazardous-location classification and loop documentation before energizing.