Features:
- Triple Modular Redundant (TMR) architecture executes 2-out-of-3 hardware voting to eliminate single points of failure.
- Provides 8 high-performance output channels, including six 4–20 mA outputs and two high-current 20–320 mA outputs.
- Integrated online hot-spare support allows module replacement without operational shutdown or field wiring disruption.
The Triconex 3806E is currently supplied in brand-new, factory-sealed surplus or fully tested refurbished condition, complete with original manufacturer hardware keying and light green color identification plate.
Engineered specifically for critical industrial processes, this module provides highly reliable analog control output signals for heavy-duty actuators, specialized control valves, and turbomachinery protection systems.
Proper installation requires pairing the module with a dedicated Basic Termination Panel (Part # 9863-710) and supplying dual redundant +24 VDC external loop power to ensure compliant high-current output drive capability.
The Triconex 3806E High Current Analog Output Module is fully supported by the manufacturer (OEM).
Triconex 3806E Analog Output Module Manuals, Datasheets, Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
- Critical industrial turbomachinery valve and governor control.
- Heavy-duty hydraulic and pneumatic positioner actuator driving.
- Safety-critical process plant shutdown and analog regulating systems.
- Monitors actual field current continuously via hardware loopback to verify commanded output state.
- Detects open-loop conditions instantly on field connections without interrupting parallel channel drive.
- Reports individual channel health and field loop status directly to Main Processors in real time.
- Designed to meet SIL 3 functional safety requirement standards in Tricon safety instrumented systems.
- Provides complete electrical channel-to-channel and channel-to-bus isolation to prevent fault propagation.
- Complies with strict industrial EMC and environmental immunity standards for high-reliability applications.
- Configured via TriStation 1130 software suite for precise channel range setup and threshold parametering.
- Supports automatic module identification and software version verification upon chassis insertion.
- Allows channel-by-channel output range assignment and dynamic trip limit parameter configuration.