Features:
- Up to sixteen thermocouple or millivolt signals, or fifteen RTDs, share one hazardous-area transmitter.
- Two redundant twisted-pair highways carry both operating power and multiplexed measurements toward the safe area.
- The MTL838B-MBF receiver converts field measurements and status into Modbus serial data.
Eaton MTL831B concentrates low-level sensor signals before they cross the hazardous-area boundary.
The two highway pairs of MTL831B provide independent routes between the field transmitter and safe-area receiver.
RTD bank switches on MTL831B align the terminal circuit with two-, three-, or four-wire sensors.
The Eaton MTL831B Intrinsically Safe Analogue Multiplexer Transmitter may still be available for purchase and support from Apter Power beyond End-Of-Life (EOL) by the manufacturer (OEM).
Eaton MTL831B Intrinsically Safe Analogue Multiplexer Transmitter Manuals,Datasheets,Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Thermocouple, Millivolt and RTD Paths
- Low-level inputs: Sixteen positions accept thermocouple, millivolt, or supported potentiometer signals.
- RTD capacity: Fifteen positions accept two-, three-, or four-wire resistance sensors.
- Mixed measurement: Thermocouple and RTD measurements may share the transmitter under the documented terminal rules.
- Terminal groups: Sensor terminals I1 through I16 remain separate from the highway and excitation connections.
Wiring Mode and Excitation Chain
- Bank division: RTD inputs are grouped as I1–I7 and I8–I15.
- Mode switch: Each bank is configured for three-wire mode or combined two-/four-wire mode.
- Mixing limit: Three-wire RTDs are not mixed with two- or four-wire RTDs in one bank without compensation.
- Open circuit effect: A break in the series excitation path can stop every RTD connected to that path.
Powered Measurement Transfer
- Dual routes: H1 and H2 provide two redundant highway connections.
- Combined path: Each twisted pair carries transmitter power and multiplexed data.
- Receiver role: MTL838B-MBF converts the received channels and status to Modbus serial data.
- Isolation boundary: An MTL3052 protects each highway where a hazardous-area transmitter connects to the safe area.
Hazardous-Area Installation
- Location: The transmitter is approved for the documented Zone 0 or Class I, Division 1 application.
- Rail option: The base clips attach to standard 35 mm DIN46277 T-section rail.
- Surface option: The adjustable base clips support flat-surface mounting with three fasteners.
- Enclosure option: ENC8 and ENC83 variants add the specified IP67 enclosure protection for exposed locations.