Features:
- Multi-interface communication design combining RS-232, RS-485, and Ethernet for flexible system integration.
- Built-in event storage with capacity for 500 system and 500 alarm records accessible via Modbus.
- Dual phase reference channels supporting synchronized signal distribution across system racks.
The ProvibTech PT2060/91 PT2060/91-A0 SIM System Interface Module is a key component in PT2060 systems, enabling communication between monitoring racks and higher-level control systems. It allows seamless data exchange between PLC, DCS, and historian platforms. The module supports multiple communication standards, ensuring compatibility with different industrial infrastructures. Its architecture simplifies system networking and centralized control. The ProvibTech PT2060/91 PT2060/91-A0 SIM System Interface Module ensures stable communication across distributed systems.
Within system configuration workflows, the ProvibTech PT2060/91 PT2060/91-A0 SIM System Interface Module plays a central role by linking configuration software with hardware modules. It enables parameter setup, channel configuration, and system adjustments through Modbus communication. The ability to manage multiple racks through a single interface improves operational efficiency. Event and alarm storage functions provide valuable historical insight. The ProvibTech PT2060/91 PT2060/91-A0 SIM System Interface Module supports structured system management.
The ProvibTech PT2060/91 PT2060/91-A0 SIM System Interface Module also contributes to signal synchronization through its dual phase reference channels. These channels distribute phase information across all monitoring modules in the rack. With defined electrical characteristics and stable signal handling, the module ensures consistent performance. Its robust physical design supports operation in industrial environments with wide temperature ranges. The ProvibTech PT2060/91 PT2060/91-A0 SIM System Interface Module remains an essential interface for communication and coordination within PT2060 systems.
The PT2060/91 PT2060/91-A0 ProvibTech SIM System Interface Module may still be available for purchase and support from Apter Power beyond End-Of-Life (EOL) by the manufacturer (OEM).
ProvibTech PT2060/91 PT2060/91-A0 SIM System Interface Module Manuals,Datasheets,Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
ProvibTech PT2060/91 PT2060/91-A0 SIM System Interface Module Specs
General
- Manufacturer ProvibTech
- Model PT2060/91 PT2060/91-A0
- Condition New Original ready stock
- Product Family PT2060/91,PT2060/40 PT2060/40-A0,PT2060/43 PT2060/43-A0
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
- Explosion-proof Certification: Complies with CSA Class I, Div 2, Groups A, B, C, D hazardous area standards, temperature group T4.
- Safety Compliance: CE marked, compliant with Electromagnetic Compatibility (EMC) and Low Voltage Directive (LVD) requirements.
- Environmental Tolerance: Operating temperature range defined as -20°C to +65°C (-4°F to 149°F), with a humidity requirement of 95% relative humidity and no condensation.
- Isolation Voltage: Internal circuitry provides electrical isolation protection up to 1000VDC, ensuring data stability in complex industrial power grid environments.
- Data Relay and Protocol Conversion: Converts raw monitoring data from various modules within the framework into Modbus RTU or Modbus TCP/IP protocols for reading by DCS or PLC.
- Phase Reference: Provides accurate key phase signals for vibration analysis of rotating machinery (such as Bode plots and polar coordinate plots).
- System Configuration Management: Acts as the configuration gateway for the entire system, downloading setting parameters, alarm limits, and logic combinations to each submodule.
- Status Indication and Alarm Summary: Displays the real-time operational health status of the entire framework via LED indicators (OK, TX/RX, Alarm) on the module panel.
- Dedicated Slot: The module must be installed in the dedicated slot on the far right of the PT2060 frame (usually Slot 16). Mixing is not permitted.
- Hardware Components: Consists of a front control module and a rear I/O interface board. Ensure the rear terminal block wiring is secure during installation.
- Keyphasor Input: Provides two independent keyphasor signal inputs for speed synchronization and phase reference for the full-frame monitoring module.
- Communication Interface: The panel integrates RS232/RS485 or Ethernet interfaces for connecting to a configuration computer (running PT2060-CFG software) or a host computer system.