Features:
- Adjusts the motor-overload setting across a 6.3 to 10 A range.
- Changes one NC and one NO auxiliary contact after a thermal trip.
- Combines phase-failure sensitivity with temperature-compensated release behavior.
The main current paths heat the release elements while the auxiliary contacts report the resulting trip to the control circuit.
Its Class 10A behavior distinguishes sustained overload from the temporary current expected during motor acceleration.
Reset selection determines whether the contactor circuit needs operator acknowledgement after the mechanism cools.
The Siemens 3UA59 40-1J Thermal Overload Relay may still be available for purchase and support from Apter Power beyond End-Of-Life (EOL) by the manufacturer (OEM).
Siemens 3UA59 40-1J Thermal Overload Relay Manuals,Datasheets,Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Relating the adjustment dial to the protected motor
- Nameplate basis: The dial is set from the motor rated current, not the upstream fuse value.
- Adjustment window: The selected current must remain within the 6.3 to 10 A range.
- Thermal response: Higher or longer overcurrent increases heating until the release operates.
- Coordination: The contactor and fuse are selected around the same motor branch but perform different duties.
Moving from overload detection to control-circuit release
- NC contact: The normally closed contact opens the contactor-control path after a trip.
- NO contact: The normally open contact changes state for an alarm or status circuit.
- Manual reset: Operator action is required before the control circuit can be restored.
- Automatic reset: The relay can reset after cooling when the selector is placed in automatic mode.
Separating overload, short-circuit and switching functions
- Overload duty: The relay responds to sustained motor overcurrent.
- Short-circuit duty: The coordinated upstream fuse clears high fault current.
- Switching duty: The contactor makes and breaks normal motor current.
- Phase loss: Unequal heating from a missing phase accelerates the overload response.
Maintaining current paths and control contacts separately
- Main terminals: Motor-branch conductors use the larger M5 terminal system.
- Auxiliary terminals: Control wiring lands on the separate M3.5 contact terminals.
- Conductor preparation: Flexible conductors require the documented end-sleeve size and clamping range.
- Single-unit mounting: The relay body is installed as the documented stand-alone arrangement for the 3UA59 frame.