Features:
- 4.3-inch 480 x 272 color display
- Key-operated interface with eight function keys
- Industrial Ethernet communication for controller data and project transfer
Siemens
6AV6647-0AJ11-3AX0 is the KP400 Basic Color PN panel for local process display and operator input in a SIMATIC HMI installation.
Its membrane keyboard separates function selection, system commands and numeric or alphanumeric entry without using a touchscreen.
The Ethernet interface carries controller communication and project transfer, while the project determines the protocol and runtime language settings.
The Siemens 6AV6647-0AJ11-3AX0 KP400 Basic Color PN HMI Panel may still be available for purchase and support from Apter Power beyond End-Of-Life (EOL) by the manufacturer (OEM).
Siemens 6AV6647-0AJ11-3AX0 KP400 Basic Color PN HMI Panel Manuals,Datasheets,Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Operator Interface
- Display: The 4.3-inch TFT presents 480 x 272 pixels in 256 colors.
- Function keys: Eight membrane keys are available for project-defined functions.
- Entry keys: System, numeric and alphanumeric keys support command and value entry.
- Touchscreen: Operation is key based; no touch input is provided.
Controller and Engineering Links
- Physical port: One Industrial Ethernet interface carries controller communication.
- PROFINET: The configured panel project can exchange data through PROFINET.
- Open protocols: EtherNet/IP and Modbus TCP are supported on the Ethernet connection.
- Project transfer: Engineering data is transferred to the panel through Ethernet.
Runtime Configuration
- User memory: One megabyte is available for the HMI project and runtime data.
- Runtime languages: A project can provide five languages during operation.
- Project languages: The engineering configuration can define as many as thirty-two languages.
- Engineering system: Panel projects are configured with the supported WinCC environment.
Panel Installation
- Orientation: Landscape mounting is supported; portrait mounting is not specified.
- Maximum inclination: Installation may tilt up to 35 degrees without external ventilation.
- Front protection: Correct panel mounting provides IP65 and NEMA 4/4X at the operator side.
- Rear protection: The cabinet side of the panel remains IP20.