Features:
- Channels: 16 module-isolated digital outputs
- Output Signal: 24 V DC current-source
- Load Current: 0.2 A per output, 3.2 A total
The SDV541-S63/PRP ordering code selects sixteen-channel isolated 24 V DC output module with signal-cable adapter, G3, -20 to 70 deg C, and false-insertion prevention pin.
Sixteen isolated current-source outputs connect through the dedicated signal-cable interface and PRP prevention pin.
Size each load within the channel and total-current limits, then verify the cable adapter and PRP key.
Availability is subject to Apter Power inventory and sourcing confirmation.
Verified resources for Yokogawa SDV541-S63/PRP:
Yokogawa SDV541-S63/PRP Specifications
General
- ManufacturerYokogawa
- ModelSDV541-S63/PRP
- ConditionNew and factory sealed
- Product FamilyProSafe-RS FIO Modules
- Interface: dedicated signal-cable adapter
- Withstand: 500 V AC with the specified cable
- Pin: PRP prevents wrong module insertion
- Per Line: 0.2 A maximum
- Aggregate: 3.2 A total output current
- Resistance: 120-685 ohm load range
- Pair: use an additional matching module without option code
- Transfer: prove field state during switchover testing
- Supply: verify the external 24 V DC source