Features:
- Controller and direct I/O: Combines loop strategy execution with onboard field channels.
- Signal flexibility: Supports current or voltage analog modes and two digital-input voltage ranges.
- Safety-critical defaults: Requires engineered output states and independent interlocks where consequences demand them.
ABB IMCOM03 serves compact control duties where one rack module must both execute a strategy and interface directly with field signals.
Its termination choices determine how those channels reach the process, while board and termination settings define the electrical mode of each path.
Commissioning should prioritize output-state behavior, because a valid control strategy alone does not guarantee a safe response during reset or failure.
For ABB IMCOM03 support, provide the termination hardware, I/O signal modes, control-strategy backup and required safe-state behavior.
ABB IMCOM03 INFI 90 Enhanced Controller Module Manuals, Datasheets, Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
ABB IMCOM03 INFI 90 Enhanced Controller Module Specs
General
- Manufacturer ABB
- Model IMCOM03
- Condition New Original ready stock
- Product Family Symphony Harmony / INFI 90
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Direct Process Channels:
- Inputs: Four analog and three isolated digital channels.
- Outputs: Two analog and four isolated open-collector digital channels.
- Signal options: 1–5 V DC, 4–20 mA and 24/125 V DC input configurations.
Strategy Resources:
- Block library: 240 addresses with fixed and reserved locations.
- Execution: Typically four and up to ten cycles per second.
- Capacity limit: Actual usable blocks depend on memory, execution time and strategy complexity.
Safe Maintenance Sequence:
- Defaults: Document analog and digital output behavior.
- Termination: Record NTCS02 or NICS01 settings and connected cables.
- Protection: Retain independent interlocks for hazardous consequences.