Ask our team:
  • Phone: +86 181 0690 9650
  • E-Mail sales1@apterpower.com
How We Verify Your Order
Before dispatch, we confirm the exact model, revision, condition, inspection requirements and shipping documents for your order.
See a real on-site verification case >>
  • Lifecycle status

    Discontinued / Obsolete by OEM
    Apter Power can align the ControlNet interface, AC supply and keypad/touch configuration with the requested spare.

2711-B6C15

/ 4.9
1001 reviews | Need a Specific Revision?
Allen-Bradley 2711-B6C15 is a PanelView Standard 600 color keypad-and-touch terminal with ControlNet communication.
In Stock
Ships by Saturday, November 14
Fast Shipping Available
Get a quick price for 2711-B6C15
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for 2711-B6C15

  • Manufacturer:
    Allen-Bradley
  • Part Number:
    2711-B6C15
  • Product Family:
    PanelView
  • Product Type:
    Color Touch Screen Operator Terminal
  • Stock:
    1
  • Resolution (Effective):
    320 x 234
  • Operator Input:
    Touch Screen + 10 Keypad Function Keys (F1-F10)
  • Primary Network:
    ControlNet
  • Secondary Port:
    RS-232 Printer / File Transfer Port
  • Input Power:
    85-264V AC (47-63 Hz)
  • Power Consumption:
    60 VA (max)
  • Non-Volatile Memory:
    240 KB
  • Application Runtime:
    170 KB
  • Backlight Life:
    50,000 hrs (1/2 life at 25°C)
  • Touch Cell Count:
    128 (16 col x 8 rows)
  • Keypad Life:
    2 million presses (Stainless steel domed)
  • Enclosure Rating:
    NEMA Type 12/13/4X (Indoor), IP65
  • Operating Temperature:
    0 to 50 °C (32 to 122 °F)
  • Storage Temperature:
    -25 to 70 °C (-13 to 158 °F)
  • Weight:
    2.02 kg
  • Estimated shipping dimensions:
    29x19.1x11.5cm
  • Tariff Code:
    8537101190
  • Country of origin:
    USA
  • Place of shipment:
    Xiamen, Fujian, China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Model Identity System Interface Service Boundaries Applications

Features:

  • PanelView 600 color display
  • Combined keypad and touch input
  • ControlNet controller interface
2711-B6C15 gives an operator both ten physical function keys and 128 application-defined touch cells on a color PanelView 600 display. This lets one terminal application assign commands to either input method.

The ControlNet connector links the terminal to a ControlLogix controller through a 1756-CNB module or to a PLC-5 on a ControlNet network. The catalog number therefore identifies a network-specific PanelView 600 configuration.

Its separate RS-232 printer/file-transfer port can connect to a printer and can transfer applications from a computer on a ControlNet terminal. COMM and FAULT indicators remain available for local status review.

For Allen-Bradley 2711-B6C15 PanelView enquiries, Apter Power can help review the ControlNet installation, terminal application and complete catalog identity.
Allen Bradley 2711-B6C15 PanelView 600 Color Touch Screen Operator Terminal Manuals,Datasheets,Link Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
  • 2711-B6C15: PanelView 600 color operator terminal
  • Combined keypad and touch-screen input
  • Ten function keys with 128 application-defined touch cells
  • Catalog communication option: ControlNet
  • 2711-B6C15: The ControlNet connector supports connection to ControlLogix through a 1756-CNB module
  • The same ControlNet option supports connection to a PLC-5 on a ControlNet network
  • A separate RS-232 printer/file-transfer port supports serial printer connection
  • On a ControlNet terminal, the RS-232 port can also transfer applications from a computer
  • 2711-B6C15: Do not assign emergency-stop or other safety-critical control solely to this terminal
  • Use separate hardwired devices for functions critical to personnel or equipment safety
  • Match the ControlNet communication option and installed network arrangement before replacement
  • Preserve the terminal application and complete catalog information for restoration work
  • 2711-B6C15: Color local operator displays built with application-defined controls and graphics
  • Machine commands initiated from physical function keys or touch-screen objects
  • Controller data exchange on an installed ControlNet network
  • Application maintenance and serial printing through the documented auxiliary RS-232 port
Description
2711-B6C15 combines a 5-inch color display with keypad and touch input, preserving both hard-key navigation and direct screen selection in an installed PanelView 600 application.

2711-B6C15 places controller communication on ControlNet and keeps an RS-232 printer/file-transfer connection as a separate service path. That separation helps maintenance distinguish a network problem from an application-transfer or peripheral issue.

2711-B6C15 is the AC-powered base configuration rather than an L1 DC variation. Carrying the ControlNet identity, supply type and saved application together gives purchasing and service teams a more reliable basis for staging a legacy spare.
Revisions

Revision Part #

Also known as

2711-B6C15 Ser A
2711-B6C15/A, Series A, Rev A
2711-B6C15 Ser B
2711-B6C15/B, Series B, Rev B
2711-B6C15 Ser C
2711-B6C15/C, Series C, Rev C
2711-B6C15X
2711-B6C15/X, Series X, Rev X
Alternative Names
2711B6C15 27II-B6CI5 27IIB6CI5 2711-86C15 2711-B6C1 2711-B6C10 2711-B6C15L1 2711-B6C15/B
Technical notes
2711-B6C15 is discontinued by Rockwell Automation. Before service or migration, confirm the ControlNet network, installed application, AC supply, panel cutout and operator-interface requirements. Published successor references support engineering review; they do not create a direct hardware or application substitution.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
If application transfer works but controller data is absent on 2711-B6C15, where should troubleshooting begin?
Begin with the ControlNet path. The RS-232 printer/file-transfer connection is separate, so a successful service transfer does not prove that the network link is healthy.
Can a buyer use an RS-232 (DF1) PanelView 600 in place of 2711-B6C15?
No. This catalog code is the ControlNet configuration; a DF1 terminal changes the controller interface and is not a like-for-like communications spare.
Should 24 V DC be applied to 2711-B6C15 when its catalog label has no L1 suffix?
No. The base keypad/touch catalog is AC powered, while L1 identifies a DC variation. Stop and match the supply code before energizing the terminal.
What should a controls engineer prove after replacing 2711-B6C15 on an existing ControlNet segment?
Prove that the terminal joins the intended ControlNet configuration and exchanges live application data; a powered display alone is not evidence of network commissioning.
Can a touch-only PanelView 600 preserve every operator action assigned to 2711-B6C15?
Not automatically. The B catalog code combines keypad and touch input, so the replacement workflow must retain functions assigned to both physical keys and screen objects.
A repaired 2711-B6C15 prints correctly but shows no process data; does that clear the communications hardware?
No. Printing uses the auxiliary RS-232 path, while process data arrives through ControlNet. Diagnose the network connection and application configuration independently.