Ask our team:
  • Phone: +86 181 0690 9650
  • E-Mail sales1@apterpower.com
  • Lifecycle status

    Active / Available from OEM
    Apter Power coordinates quotation, backup-scope review, technical documentation, and procurement support.

2711R-T10T

/ 4.9
1001 reviews | Need a Specific Revision?
Large-format PanelView 800 touch HMI for CCW visualization, secure operation, alarms, recipes, and supported controller links.
In Stock
Ships by Wednesday, October 28
Fast Shipping Available
Get a quick price for 2711R-T10T
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for 2711R-T10T

  • Manufacturer:
    Allen-Bradley
  • Part Number:
    2711R-T10T
  • Product Family:
    PanelView
  • Product Type:
    PanelView 800 HMI Terminal
  • Stock:
    1
  • Display Size:
    10 in.
  • Operator Input:
    Analog resistive touch
  • Display Type:
    Color TFT LCD
  • Resolution:
    800 × 600 SVGA
  • Input Voltage:
    18...32 V DC
  • Maximum Power:
    14 W
  • Communication:
    10/100 Ethernet and isolated serial ports
  • Configuration Software:
    Connected Components Workbench 8.0 or later
  • Weight:
    1.64 kg
  • Estimated shipping dimensions:
    22.5 × 28.7 × 5.5 cm
  • Tariff Code:
    8537101190
  • Country of origin:
    China
  • Place of shipment:
    Xiamen,Fujian,China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Fit User Data Product Applications

Features:

  • Large operator canvas: 10-inch SVGA touch display
  • Runtime controls: passwords, users, screen rights, and firmware-dependent VNC
  • Application data: recipes, alarms, trends, and removable-media workflows

The 10-inch model provides the most vertical and horizontal working area within the current PanelView 800 range.

Its larger interface is useful only when application objects, permissions, alarms, and trends are redesigned and validated for that workspace.

Power quality and file recovery deserve a planned service procedure because both affect restart behavior and outage duration.

Apter Power offers official-data review, quotation coordination, and sourcing assistance for 2711R-T10T.

Verified resources for 2711R-T10T:

Important Notice: Confirm the required firmware, application files, cables, accessories, and documentation in the quotation before ordering.
  • Project canvas: design for 800 × 600 rather than stretching a T7 or T4 screen blindly.
  • Panel opening: use the official 10-inch cutout and mounting pattern.
  • Operator reach: position frequently used controls where they remain visible and accessible.
  • Acceptance: review navigation, alarms, trends, and touch targets with production operators.
  • Terminal password: set and retain the authorized maintenance credential.
  • User accounts: assign only the rights needed for each runtime role.
  • Protected mode: prevent unauthorized design or terminal-setting changes.
  • Remote access: enable VNC only on a documented supported firmware revision and test the password.
  • Recipe files: preserve ingredient definitions and controller mappings with the application backup.
  • Trend logging: confirm tags, sample behavior, and storage before relying on historical data.
  • Alarm archive: export retained history before restoring or replacing the terminal.
  • Transfer check: verify USB or microSD files on a workstation before the maintenance window.
  • Material-handling stations: provide a large touch workspace for status, alarms, and machine commands.
  • Air-handling control: present trends, recipes, and controller values from a local 10-inch HMI.
  • CompactLogix or Micro800 systems: run CCW applications through a documented supported protocol.
Description

A 10-inch 800 × 600 touch workspace makes 2711R-T10T the largest PanelView 800 configuration in this batch for local machine status, commands, alarm lists, and trends.


User accounts, access rights, terminal passwords, and optional VNC behavior give 2711R-T10T a broader operational-security task than simply displaying controller tags.


During recovery, 2711R-T10T can use saved applications, recipe files, alarm history, USB or microSD media, and startup diagnostics, provided firmware and file versions are recorded before service.

Alternative Names
Allen-Bradley 2711R-T10T AB 2711R-T10T 2711R T10T 2711RT10T 2711R-T10T PanelView 800 PanelView 800 10-inch touch terminal
Technical notes
Budget the DC source for the 14 W maximum demand of 2711R-T10T and verify 18...32 V DC at the terminal during startup. If the large HMI restarts intermittently, measure supply sag under load, inspect wiring and grounding, then review the power and diagnostic LEDs before reloading firmware or replacing the terminal.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
Why should a 2711R-T7T project not be reused unchanged on 2711R-T10T?
The target changes from 800 × 480 to 800 × 600 and the panel opening is different. Rework the application canvas and cutout plan, then validate navigation, alarms, trends, and touch targets on the large terminal.
How should user rights be tested on 2711R-T10T before production release?
Log in as each role and prove access to allowed screens, blocked screens, terminal settings, recipes, and commands. Correct any excess privilege before enabling the runtime on the machine.
What can make VNC unavailable on 2711R-T10T after a firmware change?
VNC support depends on revision: the manual identifies 4.011 through 7.011 and a specific 8.012 path for terminals shipped with 8.011. Confirm that boundary and the configured password before troubleshooting the network.
How should a no-start condition on 2711R-T10T be traced?
Measure 18...32 V DC at the terminal during startup, inspect the power and diagnostic LEDs, and observe the splash screen. Correct supply sag or wiring faults before attempting a firmware restore.
When must a removable-media firmware update on 2711R-T10T be stopped?
Do not begin without stable power and the correct firmware package, and never remove the USB drive or microSD card while the update runs. An interrupted update can corrupt firmware and make the terminal unusable.
What information should accompany a 2711R-T10T replacement request?
Send firmware revision, controller and protocol, application and recipe backups, panel dimensions, power symptoms if failed, label photos, quantity, destination, and required date.