Ask our team:
  • Phone: +86 181 0690 9650
  • E-Mail sales1@apterpower.com
  • Lifecycle status

    Active / Available from OEM

    Apter Power supplies 3500/92-04-01-01 as a current Ethernet/RS485 gateway configuration documented in the 3500/92 ordering table. Verify firmware and register-map requirements.

3500/92-04-01-01

/ 4.9
1001 reviews | Need a Specific Revision?
3500/92-04-01-01 is an Ethernet/RS485 Modbus communication gateway with CSA/NRTL/C approval.
In Stock
Ships by Friday, October 30
Fast Shipping Available
Get a quick price for 3500/92-04-01-01
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for 3500/92-04-01-01

  • Manufacturer:
    Bently Nevada
  • Part Number:
    3500/92-04-01-01
  • Product Family:
    3500 System
  • Product Type:
    3500/92 Communication Gateway
  • Stock:
    1
  • Current order template:
    3500/92-AA-BB-CC
  • I/O module:
    04, Ethernet/RS485 Modbus
  • Memory type:
    01, low memory
  • Agency approval:
    01, CSA/NRTL/C
  • Network protocol:
    Modbus/TCP over Ethernet
  • Serial protocol:
    Modicon Modbus over RS485
  • Rack space:
    One full-height front slot plus rear I/O
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Specifications Ordering Code System Matching Installation

Product overview:

  • Gateway for integrating 3500 rack values and statuses
  • Ethernet Modbus/TCP plus RS485 serial Modbus
  • Low-memory configuration with CSA/NRTL/C approval

3500/92-04-01-01 transfers selected rack data to control and automation systems without replacing the independent machinery-protection functions.

Plan firmware, register mapping, addressing, serial termination and network-security settings as part of the integration.

Verified resources for Bently Nevada 3500/92-04-01-01:

Additional technical data:

  • Complete rack update time: no more than 1 second
  • Operating temperature: -30 to +65 deg C
  • Main module dimensions: 241 x 24.4 x 242 mm
  • Main module weight: 0.82 kg
  • Maximum documented RS485 cable run: 4000 ft

Ordering structure:

  • AA 04 selects Ethernet/RS485 Modbus I/O
  • BB 01 selects low memory
  • CC 01 selects CSA/NRTL/C approval
  • The front gateway and rear I/O module must be supplied as a compatible pair

Compatibility checklist:

  • Use the Ethernet/RS485 rear I/O module
  • Verify main-module and I/O firmware compatibility
  • Map required rack values with the configurable Modbus register utility
  • Confirm host protocol, serial topology and Ethernet addressing

Installation checks:

  • Install the front and rear modules in the same rack position
  • Terminate and bias the RS485 network according to the design
  • Apply approved IP addressing and network hardening
  • Validate every required register and alarm state at the host
Description

3500/92-04-01-01 is a Bently Nevada 3500 Communication Gateway that exposes rack monitored values and statuses to process-control and automation systems. Option 04 selects an Ethernet/RS485 Modbus I/O module, option 01 selects low memory and the final 01 field specifies CSA/NRTL/C approval.

The module supports Modbus/TCP, serial Modicon Modbus and proprietary communications used by 3500 configuration and data-acquisition software. Confirm firmware compatibility, register mapping, RS485 topology, network addressing and host-system requirements before commissioning.

Alternative Names
3500/92-04-01-01 3500 92 04 01 01 3500-92-04-01-01 Bently Nevada 3500/92-04-01-01 Bentley Nevada 3500/92-04-01-01 Bently Nevada 3500 92 04 01 01 3500 System 3500/92-04-01-01 3500/92-04-01-01 Communication Gateway
Technical notes
3500/92-04-01-01 requires the matching Ethernet/RS485 rear I/O module. Older gateway firmware may need an upgrade before it can communicate with a newer I/O module.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
Which interfaces are provided by 3500/92-04-01-01?
Option 04 combines Ethernet with an RS485 Modbus serial interface.
What memory option is selected?
The middle 01 field identifies the low-memory configuration.
Which industrial protocols are supported?
The gateway supports Modbus/TCP, serial Modicon Modbus and proprietary Bently Nevada host communications.
What rack data can be transferred?
Configured monitored values, module statuses and alarm states can be integrated with a process-control or automation host.
Can an older gateway use a new rear I/O module?
Review the firmware revision first; older main modules may require the specified firmware upgrade kit.
How long can an RS485 network be?
The official cabling guidance permits total RS485 runs up to 4000 ft when topology, termination and cable selection are correct.
Where are register and hardware details documented?
The Manuals tab links to an Apter-hosted 3500/92 technical reference.
What information is required for pricing?
Provide firmware, rear I/O part number, protocol, register-map requirement, cable length, approvals, quantity and destination.