Features:
- Processes 3300 NSv proximity probe gap voltages into a linear 4-20 mA current output for thrust measurement.
- Factory-calibrated to a full-scale axial displacement range of 0.6 to 0 to 0.6 mm (25 to 0 to 25 mil).
- Includes a 35 mm DIN rail base and CSA/NRTL/C Class I Div 1 / Div 2 hazardous location certifications.
Order configuration 991-06-70-03-05 specifies a 0.6-0-0.6 mm displacement scale, 7.0-meter system electrical length,35 mm DIN rail mounting bracket, and CSA/NRTL/C hazardous area safety rating.
Engineered for direct control cabinet installation, this 2-wire loop-powered transmitter converts non-contact eddy current probe voltage signals into a 4-20 mA current loop without requiring rack-mounted monitoring hardware.
Correct operation requires wiring to a matched 7.0-meter 3300 NSv eddy current probe and extension cable assembly to prevent measurement scale factor errors across the axial position range.
Availability: Standard Dispatch - Verified In Stock
Bently Nevada 991-06-70-03-05 Thrust Transmitter Manuals,Datasheets,Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
- Monitors thrust bearing position and axial shaft movement in boiler feed water pumps.
- Tracks rotor position changes in high-speed multistage centrifugal gas compressors.
- Detects axial shaft displacement in small industrial steam turbines and generator sets.
- Pairs exclusively with Bently Nevada 3300 NSv proximity sensors and matching extension cables.
- Requires a total electrical system cable length of 7.0 meters (-70 option) for accurate signal conditioning.
- Connects directly to standard PLC, DCS, or SCADA analog input cards supporting 4-20 mA current loops.
- Hardwired factory calibration sets the 4-20 mA output response across the 0.6-0-0.6 mm measurement scale.
- Includes non-interacting potentiometers on the front panel for field-adjusting 4 mA zero and 20 mA span points.
- Operates without software programming or digital configuration utilities required during initial system commissioning.
- Supplies a buffered dynamic voltage output via front-panel BNC terminals for portable vibration analyzer connection.
- Protects field wiring connections from physical shock and environmental debris using transparent plastic terminal covers.
- Features built-in surge rejection and reverse-polarity power protection to prevent circuit damage during field wiring.