Ask our team:
  • Phone: +86 181 0690 9650
  • E-Mail sales1@apterpower.com
  • Lifecycle status

    Active / Available from OEM
    Apter Power supports quotation, sourcing, documentation, and DeltaV PK750 configuration review.

KL2002X1-BC1

/ 4.9
1001 reviews | Need a Specific Revision?
Emerson KL2002X1-BC1 is a DeltaV PK750 controller spare with a 750-DST capacity for simplex or redundant PK Controller nodes.
In Stock
Ships by Wednesday, October 28
Fast Shipping Available
Get a quick price for KL2002X1-BC1
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for KL2002X1-BC1

  • Manufacturer:
    Emerson
  • Part Number:
    KL2002X1-BC1
  • Product Family:
    DeltaV
  • Product Type:
    PK750 Controller
  • Stock:
    1
  • Controller size:
    PK750
  • DST limit:
    750
  • Ethernet devices (P01):
    64
  • PROFINET devices (PN1):
    150 with v15.FP1/FP2; 250 with v15.FP3 or later
  • Batch units (standalone):
    8
  • Controller input through carrier:
    +24 VDC +/-10% at 350 mA maximum
  • Power dissipation:
    7.5 W simplex; 15 W redundant
  • Operating temperature:
    -40 to 60 deg C (-40 to 140 deg F)
  • Protection rating:
    IP20, NEMA 12
  • Tariff Code:
    Please confirm the destination before shipping.
  • Country of origin:
    USA
  • Place of shipment:
    Xiamen,Fujian,China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Applications Communication Performance Compatibility

Features:

  • Spare model: KL2002X1-BC1
  • Controller size: PK750 with a 750-DST limit
  • Ethernet capacity: 64 P01 devices and up to 250 PN1 devices
The current ordering configuration is the KL2002X1-BC1 PK750 controller spare listed by Emerson for the DeltaV PK Controller platform.

It executes process control logic using local I/O and Ethernet device signals and can operate in simplex or redundant controller nodes.

Match the installed PK750 identity and confirm the carrier, bulk power supply, DeltaV version, redundancy arrangement, and required communication licenses before replacement.

Availability is subject to Apter Power inventory and sourcing confirmation.
Verified resources for Emerson KL2002X1-BC1:
  • Standalone process units engineered with PK Controller Engineering Software.
  • Integrated DeltaV systems using traditional I/O, Electronic Marshalling, WirelessHART, or Ethernet devices.
  • Simplex or redundant process-control nodes installed near equipment or in central marshalling architectures.
  • Port P01 supports as many as 64 Ethernet devices.
  • Native Ethernet functions include Modbus TCP Client, EtherNet/IP Scanner, and OPC UA Server.
  • The PK750 executes process logic using both local I/O and Ethernet device signals.
  • The PK750 controller provides a documented limit of 750 DSTs.
  • Port PN1 supports 150 PROFINET devices with DeltaV v15.FP1 or v15.FP2 and 250 with v15.FP3 or later.
  • A standalone PK750 controller supports as many as eight batch units.
  • KL2002X1-BC1 can operate in simplex or redundant PK750 controller nodes.
  • A PK Controller carrier, dedicated system bulk power supply, and engineering software are required.
  • Confirm the DeltaV release and required Ethernet or PROFINET licenses before replacement.
Description
KL2002X1-BC1 is the Emerson DeltaV spare model for the PK750 Controller. It provides a 750-DST capacity and supports 64 Ethernet devices on port P01, plus 150 PROFINET devices with DeltaV v15.FP1/FP2 or 250 with v15.FP3 or later.

The controller executes process control logic from local I/O and Ethernet device signals. Native communications include Modbus TCP, EtherNet/IP scanner, OPC UA Server, and PROFINET controller functions.

A PK Controller carrier, dedicated system bulk power supply, and PK Controller Engineering Software or DeltaV software are required. Confirm the DeltaV version, redundancy arrangement, and required PROFINET or Ethernet device licenses before ordering.
Alternative Names
KL2002X1-BC1 KL2002X1 BC1 PK750 Controller Emerson DeltaV PK750 Controller
Technical notes
KL2002X1-BC1 is the PK750 controller spare, not a complete PK0750S or PK0750R assembly. Verify the carrier, power supply, DeltaV version, licenses, and installed controller identity before replacement.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
Which controller assemblies use the KL2002X1-BC1 PK750 spare?
Emerson lists PK0750S and PK0750R assemblies, plus PK0750S-B and PK0750R-B variants without traditional local I/O power modules.
Can KL2002X1-BC1 be used in simplex and redundant nodes?
Yes. The PK750 controller size supports both simplex and redundant DeltaV PK Controller node arrangements.
Can Modbus TCP Client and EtherNet/IP Scanner run together on P01?
No. Emerson states that P01 can run either the Modbus TCP Client or the EtherNet/IP Scanner, but not both simultaneously.
Which DeltaV version is required for PROFINET S2 devices?
PROFINET S2 functionality requires DeltaV v15.FP3 or later; v15.FP1 and v15.FP2 support S1 devices.
What hardware is required with the KL2002X1-BC1 controller spare?
A PK Controller carrier and dedicated system bulk power supply are required, together with the applicable PK Controller Engineering Software or DeltaV software.
What should be confirmed before replacing a PK750 controller?
Confirm KL2002X1-BC1 on the installed controller, the redundancy role, project backup, carrier, power, DeltaV version, and required licenses.