Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for IC660BBA023

  • Manufacturer:
    General Electric
  • Part Number:
    IC660BBA023
  • Product Family:
    GE Genius I/O
  • Product Type:
    24/48 VDC Thermocouple 6 Input Block
  • Stock:
    1
  • Input Circuits:
    6 thermocouple-compatible inputs
  • Group Arrangement:
    3 isolated groups of 2
  • Thermocouple Types:
    J, K, T, E, B, R, S, and N
  • Voltage Measurement Range:
    -25.0 mV to +150 mV
  • Group-to-Group Isolation:
    300 V
  • Block-to-Block Isolation:
    1500 V for one minute
  • Input Update Time:
    2.0 s typical, 3.0 s maximum
  • Diagnostics:
    Open wire, overrange, underrange, high/low alarms, internal fault
  • Control Power:
    18-56 VDC at 9 W
  • Weight:
    4 lbs (1.8 kg)
  • Estimated shipping dimensions:
    22.44 x 8.89 x 10.00 cm
  • Tariff Code:
    8538900000
  • Country of origin:
    United States
  • Place of shipment:
    Xiamen,Fujian,China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Specifications Compensation Input Types Diagnostics

Features:

  • Monitors six thermocouple inputs arranged in three isolated groups of two.
  • Supports J, K, T, E, B, R, S, and N thermocouple types plus low-level voltage measurement.
  • Provides internal, external, or user-defined cold-junction compensation for each channel.
Remote compensation signals can represent junction temperature as 1.0 mV per degree Celsius or 1.0 µA per kelvin.

All six channels update in 2 seconds typical and 3 seconds maximum, with open-wire response under 5 seconds.

The 24/48 VDC block communicates measurements and channel status over the Genius bus while keeping its input groups separated.

The General Electric IC660BBA023 24/48 VDC Thermocouple 6 Input Block remains a possible Apter Power sourcing option for legacy temperature systems after manufacturer End-of-Life (EOL).
General Electric IC660BBA023 24/48 VDC Thermocouple 6 Input Block Manuals, Datasheets, Links

Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.

General Electric IC660BBA023 24/48 VDC Thermocouple 6 Input Block Specs

General

  • ManufacturerGeneral Electric
  • ModelIC660BBA023
  • ConditionNew Original ready stock
  • Product FamilyGE Genius I/O

Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.

Cold-Junction Methods

  • Internal Sensor: Uses the block's internal cold-junction sensor.
  • External XJV: Accepts 1.0 mV per degree Celsius from a remote junction.
  • External XJI: Accepts 1.0 µA per kelvin from a remote junction.
  • User Value: Allows a configured cold-junction compensation value.
  • Channel Adjustment: Permits input adjustment up to ±100.0°C or ±100.0°F.

Supported Temperature Signals

  • Thermocouples: Supports J, K, T, E, B, R, S, and N types.
  • Low-level Voltage: Measures signals from -25.0 mV to +150 mV.
  • Linearization: Applies type-specific thermocouple linearization.
  • Grouping: Uses three isolated groups with two measurement channels each.

Temperature Input Monitoring

  • Open Wire: Detects disconnected thermocouple circuits.
  • Range Status: Reports overrange and underrange conditions.
  • Alarm Limits: Provides high and low input alarms.
  • Internal Fault: Reports internal block faults.
  • Response: Open-wire detection responds in less than 5 seconds.
Description
With IC660BBA023, the controller receives each configured channel as linearized temperature data or as a low-level millivolt measurement for direct process use.

Individual IC660BBA023 channels can apply a measurement adjustment of up to ±100.0°C or ±100.0°F, allowing the configured indication to be aligned with the installed sensing circuit.

Fault reporting on IC660BBA023 can be enabled or disabled by circuit, so open-wire, range, alarm, and internal conditions can be included selectively in Genius bus diagnostics.

The complete IC660BBA023 block operates from 18-56 VDC at 9 W maximum and uses the 24/48 VDC power version of the thermocouple electronics and terminal assembly.
Alternative Names
General Electric IC660BBA023 GE Fanuc IC660BBA023 GE IC660BBA023 IC-660-BBA-023 IC660 BBA 023 IC660BBA023 Genius I/O Block IC660BBA023 Datasheet IC660BBA023 Technical Manual
Technical notes
IC660BBA023 accepts remote cold-junction compensation as either 1.0 mV/°C or 1.0 µA/K, which determines the required external reference signal.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
Which cold-junction reference can IC660BBA023 accept?
IC660BBA023 can use its internal sensor, a 1.0 mV/°C external voltage reference, a 1.0 µA/K external current reference, or a configured compensation value.
Why might IC660BBA023 report an open-wire condition?
IC660BBA023 checks the thermocouple circuit for an open connection and normally reports that condition within less than 5 seconds.
Can IC660BBA023 measure millivolt signals instead of temperature?
Yes. IC660BBA023 supports low-level voltage measurement from -25.0 mV to +150 mV in addition to the supported thermocouple types.
How are the six IC660BBA023 channels isolated?
IC660BBA023 arranges the inputs as three groups of two, with 300 V group-to-group isolation and 1500 V block-to-block isolation.
What should be supplied for an IC660BBA023 quotation?
Send the complete IC660BBA023 code, quantity, destination, and any terminal or electronics assembly details visible on the installed block.
Which thermocouple selections are available on IC660BBA023?
IC660BBA023 supports J, K, T, E, B, R, S, and N thermocouple characteristics, selected independently by channel.
Where can the official IC660BBA023 technical information be reviewed?
The IC660BBA023 Manuals tab provides the General Electric technical manual together with internal product and support links.