Features:
- Monitors six thermocouple inputs arranged in three isolated groups of two.
- Supports J, K, T, E, B, R, S, and N thermocouple types plus low-level voltage measurement.
- Provides internal, external, or user-defined cold-junction compensation for each channel.
Remote compensation signals can represent junction temperature as 1.0 mV per degree Celsius or 1.0 µA per kelvin.
All six channels update in 2 seconds typical and 3 seconds maximum, with open-wire response under 5 seconds.
The 24/48 VDC block communicates measurements and channel status over the Genius bus while keeping its input groups separated.
The General Electric IC660BBA023 24/48 VDC Thermocouple 6 Input Block remains a possible Apter Power sourcing option for legacy temperature systems after manufacturer End-of-Life (EOL).
General Electric IC660BBA023 24/48 VDC Thermocouple 6 Input Block Manuals, Datasheets, Links
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
General Electric IC660BBA023 24/48 VDC Thermocouple 6 Input Block Specs
General
- ManufacturerGeneral Electric
- ModelIC660BBA023
- ConditionNew Original ready stock
- Product FamilyGE Genius I/O
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Cold-Junction Methods
- Internal Sensor: Uses the block's internal cold-junction sensor.
- External XJV: Accepts 1.0 mV per degree Celsius from a remote junction.
- External XJI: Accepts 1.0 µA per kelvin from a remote junction.
- User Value: Allows a configured cold-junction compensation value.
- Channel Adjustment: Permits input adjustment up to ±100.0°C or ±100.0°F.
Supported Temperature Signals
- Thermocouples: Supports J, K, T, E, B, R, S, and N types.
- Low-level Voltage: Measures signals from -25.0 mV to +150 mV.
- Linearization: Applies type-specific thermocouple linearization.
- Grouping: Uses three isolated groups with two measurement channels each.
Temperature Input Monitoring
- Open Wire: Detects disconnected thermocouple circuits.
- Range Status: Reports overrange and underrange conditions.
- Alarm Limits: Provides high and low input alarms.
- Internal Fault: Reports internal block faults.
- Response: Open-wire detection responds in less than 5 seconds.