Features:
- Drives six independently controlled 4-20 mA output circuits from one Genius I/O block.
- Allows outputs 5 and 6 to serve voltage applications in addition to current-loop service.
- Provides isolated loop power, configurable scaling, and output feedback diagnostics.
Current applications support loads up to 850 ohms, and the two voltage-capable circuits can produce 0-5 V or higher-voltage ranges within the documented limits.
The output channels share BSM circuitry but remain isolated from the rest of the block, with 1500 V block-to-block isolation.
IC660BBA025 operates from 18-56 VDC and can switch the 24/48 VDC IC660BSM021 for redundant bus installations.
For legacy analog-output requirements, the General Electric IC660BBA025 24/48 VDC Current-source Analog 6 Output Block may remain purchasable through Apter Power beyond OEM EOL.
General Electric IC660BBA025 24/48 VDC Current-source Analog 6 Output Block Manuals, Datasheets, Links
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
General Electric IC660BBA025 24/48 VDC Current-source Analog 6 Output Block Specs
General
- ManufacturerGeneral Electric
- ModelIC660BBA025
- ConditionNew Original ready stock
- Product FamilyGE Genius I/O
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Current and Voltage Service
- Current Loops: All six channels control 4-20 mA devices.
- Voltage Use: Outputs 5 and 6 can be configured for voltage applications.
- Loop Power: The block supplies power for each output loop.
- Isolation: Loop power remains isolated from the rest of the block.
Command Value Processing
- Engineering Units: Each output can use configured linear scaling.
- Resolution: Current commands are resolved in 6 µA increments.
- Update Rate: The block updates output values every 25 ms.
- Hold Behavior: Outputs can hold their last state or use a configured default.
Output Verification
- Range Status: Reports output overrange and underrange.
- Feedback Error: Detects feedback current below the expected value.
- Feedback Time: Allows a configured delay before declaring feedback failure.
- Fault Reporting: Can be enabled or disabled for each circuit.
- Redundancy: Includes a digital output for the IC660BSM021 bus switch module.