Features:
- Thirteen compact box-clamp terminals
- Shared internal bus for one circuit potential
- Different limits for single and paired conductors
With thirteen positions,
IC670TBM002 offers more connection points than the barrier-style accessory while keeping the conductors on one common node.
The box-clamp design accommodates a broad single-wire range, but paired conductors have a smaller maximum size than single conductors.
The chosen potential should be labeled at the block and checked for continuity before field power is applied, because none of the thirteen positions is isolated from the others.
The General Electric IC670TBM002 Auxiliary Terminal Block with Box-Style Terminals may remain available for quotation and legacy-system support through Apter Power.
General Electric IC670TBM002 Auxiliary Terminal Block with Box-Style Terminals Manuals, Datasheets, Links
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
General Electric IC670TBM002 Auxiliary Terminal Block with Box-Style Terminals Specs
General
- ManufacturerGeneral Electric
- ModelIC670TBM002
- ConditionNew Original ready stock
- Product FamilyField Control Distributed I/O
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Box-Terminal Capacity
- Positions: Thirteen box-style terminals are provided.
- Single conductor: One AWG 14 through AWG 22 wire may be landed per position.
- Paired conductors: Two wires up to AWG 18 may share a terminal.
- Preparation: Strip conductors to the documented length and keep strands inside the clamp.
Shared Electrical Node
- Internal common: Every terminal is connected to the same internal bus.
- Return wiring: The block can distribute a common return when the circuit design allows.
- Ground wiring: A designated ground network may use the auxiliary points.
- Circuit separation: Do not combine isolated or different-voltage networks on one block.
Mounting and Inspection
- Attachment: Fit the block to the compatible Field Control terminal assembly.
- Clearance: Allow access for tightening and later inspection.
- Torque review: Secure terminals according to the applicable wiring practice.
- Power-up check: Verify continuity and the intended potential before energizing loads.