Features:
- Attenuates three AC-phase measurements and both DC-bus measurements through separate divider strings.
- Uses the documented Group 2 resistor-and-jumper population for multiple nominal bridge voltages.
- Routes five scaled feedback outputs through a single protected JV ribbon interface.
Each divider channel on DS200NATOG2A remains electrically distinct from input terminal to scaled output, allowing a single phase or bus path to be traced without treating all five readings as one circuit.
Group 2 hardware changes the lower two positions of every divider chain from resistors to wire jumpers, and the selected stab pattern establishes the permitted nominal input level.
The receiving board completes each feedback circuit with a burden resistor, while a local metal-oxide varistor limits the DS200NATOG2A output if the ribbon connection is interrupted.
The General Electric DS200NATOG2A Voltage Feedback Scaling Board may still be available for purchase and support from Apter Power beyond End-Of-Life (EOL) by the manufacturer (OEM).
General Electric DS200NATOG2A Voltage Feedback Scaling Board Manuals,Datasheets,Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Following each bridge measurement through the board
- AC coverage: Three independent strings accept the three phase-related bridge voltages.
- DC coverage: Two further strings carry the positive-bus and negative-bus measurements.
- Channel identity: The manual labels the five divider networks A through E so a suspect reading can be traced by path.
- Receiving load: A burden resistor on the gate distribution and status board completes each scaled feedback circuit.
Relating Group 2 hardware to the bridge level
- Network population: Each DS200NATOG2A divider contains four series resistors and two wire-jumper positions.
- Highest setting: The published Group 2 table includes a 4200 V nominal input arrangement.
- Intermediate setting: A separate factory jumper pattern is documented for a 2200 V nominal bridge input.
- Lower setting: The remaining listed configuration scales a 1200 V nominal input; the installed stabs must match the required row.
Checking the shared scaled-output connection
- Header: The five low-level feedback signals leave DS200NATOG2A through the 20-pin JV connector.
- Cable route: A ribbon cable carries the outputs to the associated gate distribution and status board.
- Open-path response: Local metal-oxide varistors limit output voltage when the ribbon load is removed.
- System check: A multi-channel shift should be compared with the common JV cable and receiving-board connection before divider components are blamed.
Observing the manufacturer service boundaries
- Hazard level: Lethal potentials are present on DS200NATOG2A while the bridge and board are operating.
- Test points: TP1 through TP5 are reserved for factory test and are not routine field measurement points.
- Power isolation: Input power must be turned off before the board or its connected circuits are handled.
- Repair limit: The instructions identify no end-user serviceable parts, so damaged assemblies should follow the manufacturer return process.