Features:
- Automatic testing during operation verifies output conditions, cross-talking, and safety shutdown performance.
- Eight safety-related channels support SIL 3 applications and provide reliable switching for loads up to 500 mA.
- Integrated safety shutdown, safe isolation, line monitoring, and short-circuit-proof outputs enhance operational security.
Reliable output management is essential in safety systems, and HIMA F3349 provides eight monitored channels for controlling external loads. Each channel supports resistive or inductive devices with currents up to 500 mA and can also operate lamp loads up to 10 W. Output voltage is determined by the external 24 V DC or 48 V DC supply connected through the cable plug. Compact dimensions requiring only 4 SU make installation straightforward.
Continuous diagnostics distinguish HIMA F3349 from conventional output modules. Automatic testing occurs during normal operation without interrupting system performance. Output signal readback, line monitoring, safety shutdown verification, and cross-talking detection through the walking-bit test contribute to dependable channel supervision. The 0-signal readback operating point remains at or below 6.5 V, providing an additional level of monitoring accuracy.
HIMA F3349 is applicable to safety-related systems requiring SIL 3 performance in accordance with IEC 61508. Safe isolation and integrated shutdown functions help maintain secure operation under abnormal conditions. Short-circuit-proof outputs further improve system reliability. Through a combination of diagnostic functions and protected output channels, HIMA F3349 supports industrial applications where availability and safety are equally important.
The F3349 HIMA 8-Channel Safety Output Module may still be available for purchase and support from Apter Power beyond End-Of-Life (EOL) by the manufacturer (OEM).
HIMA F3349 8-Channel Safety Output Module Manuals,Datasheets,Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
HIMA F3349 8-Channel Safety Output Module Specs
General
- Manufacturer HIMA
- Model F3349
- Condition New Original ready stock
- Product Family F3331,F3330,F3322
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
- System Bridging: The module employs proprietary parallel bus technology, enabling seamless motherboard-level interconnection with the central processing unit (CPU) of HIMA H41q and H51q systems.
- Front-end Linkage: It can directly receive digital commands from the front-end safety logic controller, translating software safety policies into field physical output responses within seconds.
- Isolation Protection: The internal circuitry has an opto-isolation barrier of up to 2500V between itself and external field loads, completely blocking reverse surges to the core bus.
- Extension and Collaboration: It supports paired cascading with relay amplifier modules such as the F3421, enabling the safe extension of low-voltage control signals to high-power, high-voltage switching physical contacts.
- Emergency Shutdown: Deployed in ESD (Emergency Shutdown System) systems in oil and gas pipelines to instantly close large safety shut-off valves (ESD valves) upon triggering overpressure.
- Boiler Explosion Protection: Used in BMS (Burner Management System) systems of large power plant boilers to control the main safety shut-off valves for gas or oil to prevent catastrophic explosions.
- Hazardous Pressure Relief: In the Safety Instrumented System (SIS) of high-pressure reactors in chemical plants, responsible for driving emergency relief valves for emergency pressure relief when process parameters exceed limits.
- Audible and visual alarm: As the terminal drive source of the key alarm chain in rail transit or high-risk workshops, it forcibly illuminates the emergency signal lights and activates the high-decibel siren when a fault occurs.
- Channel Allocation: The hardware board provides 8 independent safety digital output channels, each with control logic that can be independently addressed in the engineering configuration software.
- Load Matching: Each output channel provides a maximum drive current of 500 mA under 24 VDC conditions, supporting switching between resistive, inductive, and lamp-based modes.
- Line Monitoring: Line break and short circuit detection functions can be activated in the configuration, allowing real-time status feedback through minute monitoring current.
- Redundancy Configuration: Supports configuration as a redundant output structure via parallel dual-board connection or cross-wiring, improving system availability while ensuring compliance with the highest SIL 3 safety level.