Ask our team:
  • Phone: +86 181 0690 9650
  • E-Mail sales1@apterpower.com
  • Lifecycle status

    Active / Available from OEM
    Apter Power can check F6706 supply, prepare a quotation, and provide the HIMA references needed to validate its isolated analog-loop configuration.

F6706

/ 4.9
1001 reviews | Need a Specific Revision?
HIMA F6706 is a two-channel isolated analog output module that generates 0/4-20 mA commands for HIQuad process-control loops.
In Stock
Ships by Thursday, October 29
Fast Shipping Available
Get a quick price for F6706
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for F6706

  • Manufacturer:
    HIMA
  • Part Number:
    F6706
  • Product Family:
    HIMA HIQuad® X
  • Product Type:
    two-channel isolated analog output module
  • Stock:
    1
  • Analog outputs:
    2
  • Signal range:
    0/4-20 mA
  • Channel isolation:
    Individually electrically isolated
  • Basic error at 25 C:
    <= 0.1%
  • Operating error, 0 to 60 C:
    <= 0.4%
  • Maximum cable length:
    1000 m, burden dependent
  • Sink-mode source voltage:
    10-30 V DC
  • Dielectric strength:
    250 V to analog ground
  • Space requirement:
    4 SU
  • 5 V DC consumption:
    40 mA
  • 24 V DC consumption:
    100 mA
  • Tariff Code:
    8537101190
  • Country of origin:
    Germany
  • Place of shipment:
    Xiamen,Fujian,China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Analog Control Isolation Wiring Conversion Accuracy

Features:

  • Two galvanically separated analog output channels
  • 0/4-20 mA operation with a -20 to +20 mA option
  • Source or sink wiring, with up to 1000 m cable runs when loop limits permit
F6706 combines two precision current commands in a four-TE HIQuad module while preventing one field loop from using the other channel as an unintended return path.

Source and sink connections are both supported; an external 10-30 V DC supply is introduced when the receiving circuit requires sink operation.

Long-distance wiring is possible only after the total burden and voltage reserve are calculated for the selected current range.

HIMA F6706 two-channel isolated analog output module can be sourced through Apter Power, with official HIMA technical references available to confirm wiring and loop limits.
HIMA F6706 two-channel isolated analog output module Manuals, Datasheets, Links Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.

F6706 output ranges and load

  • Normal signal: Each channel operates as a 0/4-20 mA analog output
  • Bipolar option: An approved project may configure the output from -20 to +20 mA
  • Independent channels: Electrical separation prevents a common internal field-loop reference
  • Receiving burden: Output accuracy depends on the connected load remaining within the available voltage

F6706 isolation boundaries

  • Channel barrier: The first analog path is galvanically isolated from the second
  • External references: Cabinet wiring must not defeat the separation by joining returns unintentionally
  • Fault location: A disturbance can be traced to one loop without treating both outputs as a single circuit
  • Commissioning test: Current and polarity are checked independently at each receiving device

F6706 source and sink wiring

  • Source circuit: The module provides loop current through the designated terminal arrangement
  • Sink circuit: A 10-30 V DC external source supplies the field loop
  • Long cable: Runs up to 1000 m require a complete resistance and burden calculation
  • Front connection: Both outputs are routed through the correct HIMA plug and assigned rack position

F6706 conversion accuracy

  • Reference error: The specified basic error is no more than 0.1% at an ambient temperature of 25 °C.
  • Operating error: Across the 0 to +60 °C operating range, the stated conversion error is no more than 0.4%.
  • Digital resolution: The two analog output channels use 12-bit conversion resolution.
  • Loop constraint: Conversion accuracy applies only when the receiving burden and line resistance remain within the permitted loop limits.
Description
Two independent current-command paths are provided by HIMA F6706, an isolated analog output module for HIQuad control and safety applications.

Each F6706 channel can generate a 0/4-20 mA signal and is galvanically separated from the other output. The circuits may be wired as sources or as sinks; sink operation uses an external 10-30 V DC loop supply.

The module also supports a -20 to +20 mA operating option where the approved circuit requires bidirectional current. Cable runs may extend to 1000 m when conductor resistance, receiving-device burden, and available loop voltage remain within the permitted electrical limits.

Installation planning for F6706 therefore covers more than slot width: the two channel references must remain separated, loop polarity must match the selected mode, and both field circuits are verified individually during commissioning.
Alternative Names
F 6706 F-6706 F670 6 HIMA F6706 HIMA-F6706 HIQuad X F6706 HIMA HIQuad X F6706 F67O6
Technical notes
Preserve channel-to-channel isolation and calculate loop burden before using long F6706 cable runs; sink wiring requires an external 10-30 V DC source.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
Can the two F6706 outputs share the same field reference?
For F6706, the channels are individually galvanically isolated; external wiring should not reconnect their references unless the approved loop design explicitly requires it.
When does F6706 need an external loop supply?
In sink mode, the F6706 field circuit uses an external supply within the specified 10-30 V DC range.
May F6706 send a bipolar analog command?
On F6706, yes, the module supports a -20 to +20 mA option when that operating mode is part of the approved application.
What limits a 1000 m F6706 cable run?
For F6706, the receiving-device burden, conductor resistance, loop voltage, and selected source or sink circuit must all remain within the electrical limits.
How should a missing F6706 output be diagnosed?
With F6706, measure the commanded current, verify polarity and loop supply, inspect the front connection, and review the receiving device before replacing the module.
Can one F6706 channel be serviced without assuming the other has failed?
On F6706, yes. Because the outputs are separated, troubleshoot the affected loop and its wiring independently while still observing the system maintenance procedure.
What must match before an F6706 replacement is commissioned?
Confirm the complete F6706 type, rack position, 0/4-20 mA or bipolar configuration, source/sink mode, and each channel assignment.