Features:
- Thirty-two outputs: The official guide documents up to 32 hazardous-area channels.
- MTL4521 isolation: Sixteen loop-powered isolators provide the documented channel population.
- Defined load boundary: Honeywell lists solenoids, alarms, and simple apparatus such as LEDs.
CC-GDOL11 forms the intrinsically safe digital output boundary between Series C control logic and hazardous-area loads.
The paired-channel MTL4521 population should be checked against load current, safety documentation, LED state, and the optional CC-SDXX01 expander layout.
Procurement review must confirm CC-GDOL11 because the official model table does not list a nonredundant CC-GDOL21 product.
Availability is subject to Apter Power's current inventory and sourcing confirmation.
Honeywell CC-GDOL11 GI/IS Digital Output IOTA Manuals, Datasheets, Links
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Honeywell CC-GDOL11 GI/IS Digital Output IOTA Specs
General
- ManufacturerHoneywell
- ModelCC-GDOL11
- ConditionNew Original ready stock
- Product FamilyExperion Series C GI/IS IOTAs
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Hazardous-area load review
- Channel count: Keep the configured output scope within 32 channels.
- Output function: Use the documented 24 V DC source-output arrangement.
- Current level: Confirm the official 48 mA output boundary.
- Load type: Match solenoid, alarm, or simple apparatus requirements.
MTL4521 population
- Isolator model: Honeywell specifies the loop-powered MTL4521 IIC.
- Population: Sixteen isolators support the 32-channel IOTA.
- Power record: Use the documented 90 mA maximum at 24 V per isolator.
- Safety values: Preserve the official Vo, Io, Po, and Um data with the loop design.
Application checks
- Solenoid and alarm: Verify energization current and approved hazardous-area design.
- Simple apparatus: Honeywell includes an LED as an example.
- Expander: Confirm CC-SDXX01 only where the official layout requires it.
- Commissioning: Test output state and field response under controlled conditions.