Features:
- Provides independent 24V power feeds to CP1 and CP2 processors.
- 54cm and 77cm cables with 2×2.5mm² CC600 cable for flexible routing.
- Squeeze To Release bus bar connector with mate-n-lock chassis connector.
The FS-PDC-CPSET is a power distribution cable set specifically designed for Honeywell FSC (Fail-Safe Control) system Control Processors. It transfers 24V DC power from the mains bus bar (FS-MB-0001) to the Controller chassis, providing independent power feeds to CP1 and CP2. The FS-PDC-CPSET consists of two cables: FS-PDC-CP24-1 for CP1 and FS-PDC-CP24-2 for CP2. The FS-PDC-CPSET ensures reliable power delivery to critical safety processors, supporting redundant Control Processor configurations for high-availability applications.
The FS-PDC-CPSET includes two cables with specific lengths for different Control Processor connections: FS-PDC-CP24-1 (54cm) for CP1 and FS-PDC-CP24-2 (77cm) for CP2. The FS-PDC-CPSET uses CC600 2 × 2.5 mm² cable type, ensuring low voltage drop and reliable power delivery. The FS-PDC-CPSET's optimized lengths provide flexible routing options within control cabinets, accommodating various chassis configurations. The FS-PDC-CPSET's cable set design simplifies installation and ensures proper power distribution to both Control Processors.
The FS-PDC-CPSET features a 2-pole Squeeze To Release connector (D-TAB-200-STR) on the bus bar side, ensuring secure and reliable connection to the mains power rail. The FS-PDC-CPSET uses a 2-pole mate-n-lock connector on the SM Controller side for reliable chassis connection. The FS-PDC-CPSET has a pin allocation where pin 1 provides +24V and pin 2 provides 0V return for each processor. The FS-PDC-CPSET carries UL and CSA approvals with FM pending, ensuring compliance with international safety standards.
The FS-PDC-CPSET HONEYWELL Power Distribution Cable may still be available for purchase and support from Apter Power beyond
End-Of-Life (EOL) by the manufacturer (OEM).
HONEYWELL FS-PDC-CPSET Power Distribution Cable Manuals,
Datasheets, Drivers, Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not
included with this equipment unless listed in the above stock item description. All prices are
shown in USD.
HONEYWELL FS-PDC-CPSET Power Distribution Cable Specs
General
- Manufacturer HONEYWELL
- Model FS-PDC-CPSET
- Condition New Original ready stock
- Product Family
FS-TSFIRE-1624,FS-TPSU-2430,FS-USI-0001,FS-CPCHAS-0002 FC-CPCHAS-0002
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not
included with this equipment unless listed in the above stock item description. All prices are
shown in USD.
- Emergency Shutdown (ESD) Systems: Powers the processors responsible for initiating plant-wide safe states, isolation, and blowdown logic during major hazards.
- Burner Management Systems (BMS): Deployed in boiler control, furnace logic, and multi-burner management where control loop delays or power drops can cause catastrophic fuel explosions.
- Fire & Gas (F&G) Logic Solvers: Supports the continuous background evaluation of flame, toxic gas, and acoustic leakage data from the field.
- High-Integrity Pressure Protection Systems (HIPPS): Ensures sub-second execution speeds for downstream pipeline overpressure protection valves.
- Enclosure Rating: Designed exclusively for indoor installation within purged, dust-tight, or climate-controlled industrial marshalling cabinets (typically IP54 or NEMA 4/12 configurations).
- Operating Ambient: Assured to perform reliably from -5°C to +70°C (+23°F to +158°F) cabinet internal temperature.
- Storage/Transport: Withstands -40°C to +85°C (-40°F to +185°F).
- Operates in non-condensing relative humidity up to 95%.
- Vibration and Mechanical Shock: Built to resist low-frequency industrial floor vibrations, ensuring the heavy-duty Mate-N-Lok 2-pole pins remain firmly seated inside the controller socket.
- Dual-Bus Diagnostic Monitoring: The "SET" includes two distinct cables (Channel A and Channel B). The Safety Manager's internal diagnostic software continuously tracks the voltage status downstream of each cable.
- Fault-Tolerant Alarm Integration: If one cable breaks, experiences high resistance, or loses connection, the Safety Manager triggers a "CP Power Supply Degradation" diagnostic alarm via the Experion PKS console. This allows technicians to replace the faulty cable while the system continues running safely on the redundant branch.
- Overcurrent Isolation and Thermal Fusing: The cable connects back to the main power bus bar or a Power Distribution Board (PDB). This setup relies on integrated short-circuit current limiting and fast-acting fuses. This configuration instantly isolates a localized cable short-circuit, preventing it from pulling down the entire cabinet’s 24Vdc rail.
- Status Indicators: The processor modules supplied by the FS-PDC-CPSET utilize on-board LEDs (such as 24V OK) to give local, visual confirmation of the electrical feed status at the physical point of termination.