1001 reviews | Need a Specific Revision?
Foxboro P0914SQ is the legacy FBM201 order code for eight isolated 0–20 mA analog input channels in installed I/A Series systems.
In Stock
Ships by Saturday, October 17
Fast Shipping Available
Get a quick price for P0914SQ
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for P0914SQ

  • Manufacturer:
    Invensys
  • Part Number:
    P0914SQ
  • Product Family:
    Foxboro
  • Product Type:
    Legacy FBM201 Isolated Analog Input Module
  • Stock:
    1
  • Analog input channels:
    8, individually isolated
  • Input range:
    0 to 20 mA dc
  • HART capability:
    Electrical compatibility only
  • Input power:
    24 VDC +5/-10%
  • Maximum power consumption:
    7 W
  • Termination cable:
    Type 1, up to 30 m
  • Dimensions:
    4.5 × 10.2 × 10.4 cm
  • Operating temperature:
    -20 to 70°C at -300 to 914 m; derated above 914 m
  • Relative humidity:
    5 to 95%, non-condensing
  • Input channel isolation test:
    600 VAC for 1 minute between any channel and ground or any other channel
  • Storage temperature:
    -40 to +70°C
  • Vibration:
    0.75 g from 5 to 500 Hz
  • Weight:
    0.284 kg
  • Tariff Code:
    8538900000
  • Country of origin:
    USA
  • Place of shipment:
    Xiamen, Fujian, China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Legacy Identity Substitution Review Loop Verification Application
  • Preserve the legacy P0914SQ order identity
  • Verify the installed FBM201 TA and Type 1 cable
  • Review current-module compatibility before substitution

P0914SQ is chosen when maintaining an installed FBM201 whose spare strategy requires the original legacy hardware identity.

The documented successor does not by itself prove a drop-in exchange because baseplate, controller release and field termination still matter.

Replacement preparation should capture the original loop-power design and all eight database channel definitions.

Availability, condition, price, and shipping time for P0914SQ are confirmed during quotation.

Foxboro P0914SQ Manuals, Datasheets, Links

Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.

  • Use P0914SQ only where the installed record calls for this code
  • Record the complete module and TA labels
  • Do not erase the legacy identity when evaluating a successor
  • Confirm baseplate and controller-release support
  • Compare TA cable and connector requirements
  • Restore the exact eight-channel database definition
  • Test each channel with a traceable current source
  • Verify the original internal or external loop supply
  • Review diagnostics before releasing process interlocks
  • Legacy I/A Series analog input maintenance
  • Like-for-like FBM201 spare replacement
  • Migration planning from P0914SQ to RH914SQ
Description
Foxboro P0914SQ performs the FBM201 isolated analog-input function in legacy I/A Series installations.

It digitizes eight conventional current loops and keeps the channel circuits galvanically separated from each other, ground and module logic.

The legacy order code remains important for spare matching even though RH914SQ is identified as its current successor.
Alternative Names
P0914SQ P 0914 SQ Foxboro P0914SQ Invensys P0914SQ FBM201 P0914SQ Foxboro Evo P0914SQ Invensys Foxboro P0914SQ
Technical notes
P0914SQ is the documented Foxboro Evo order code for the FBM201 eight-channel isolated 0 to 20 mA analog input module. Before replacing it with RH914SQ, verify the installed baseplate, termination assembly, Type 1 cable and controller configuration.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
Can Foxboro P0914SQ be replaced directly by RH914SQ?
Treat RH914SQ as the documented successor, then verify the legacy baseplate, controller software, TA, connector and database before approving the exchange.
Does Foxboro P0914SQ support HART device communication?
No. It accepts the analog current from a HART loop but does not act as a digital HART host.
What should be quoted with Foxboro P0914SQ?
Confirm whether the spare requirement includes only the module or also the installed TA, Type 1 cable and baseplate hardware.
Why might Foxboro P0914SQ read all channels low after replacement?
Check the shared installation factors first: module supply, TA cable seating, loop-power arrangement, returns and restored database scaling.
Can the old TA remain connected when Foxboro P0914SQ is changed?
Usually the removable TA cable allows field wiring to remain terminated, but its part number, condition and compatibility must be confirmed.
What legacy records are needed before removing Foxboro P0914SQ?
Save the module label, slot, software release, TA and cable numbers, channel ranges, alarms, loop supplies and fault history.
How should a replacement Foxboro P0914SQ be accepted?
Inject known currents on every channel, compare readings with the archived configuration and prove alarms and control actions before normal operation.