Specifications & Approvals

The Bently Nevada 330180-12-05 is a 3300 XL Proximitor Sensor designed for a 1.0-meter 3300 XL 8 mm proximity transducer system. This configuration is supplied without mounting hardware and carries CSA, ATEX, and IECEx approvals.

Operation & Applications

Working with a compatible probe, the sensor converts the distance between the probe tip and a conductive target into a proportional voltage signal, supporting shaft vibration, axial position, Keyphasor reference, and speed measurements on rotating machinery.
Find Parts

Preventive Inspection Checklist

Inspection & Electrical Diagnostics

Routine maintenance should include inspecting the Proximitor Sensor, field wiring, probe cable, and connectors for corrosion, contamination, loose connections, physical damage, or oil ingress. Verify that the power supply remains within the specified operating range and confirm that the output signal remains stable during operation.

Optimizing Sensor Performance

For radial vibration applications, the recommended probe gap is approximately 1.27 mm (50 mils), corresponding to an output of about −9 VDC. Probe cables should never be sharply bent, and the minimum allowable bend radius is 25.4 mm (1 inch). Where the installation environment is exposed to moisture, dust, or contaminants, connector protectors are recommended to provide additional environmental protection.
  • Compact and Flexible Design.
  • Improved Electrical Protection.
  • Faster and More Reliable Wiring.

Pre-Replacement & Safety Guidelines

Before replacing a 330180-12-05, isolate the monitoring circuit and follow the facility’s lockout/tagout and hazardous-area procedures. Record the existing wiring and output readings, then disconnect the field terminals and ClickLoc connector without twisting or pulling the cable. The replacement must match the 1.0-meter total system length and the required agency approvals. Because a one-meter system does not use an extension cable, installing a sensor calibrated for a five- or nine-meter system can cause incorrect output and measurement performance.

Post-Installation & Verification

After installing the replacement, reconnect the wiring, confirm grounding and shielding, and inspect the probe-to-sensor connection.
Restore power and verify the probe gap voltage, monitor indication, alarm settings, and overall vibration trend before returning the machine to normal service.

Correct maintenance and model matching help the Bently Nevada 330180-12-05 Proximitor Sensor maintain reliable machinery protection while reducing false alarms, unexpected shutdowns, and avoidable maintenance costs.


Reference:
https://dam.bakerhughes.com/m/23d2a1de24360b13/original/3300-XL-8mm-Proximity-Transducer-System-Datasheet-141194-pdf.pdf

More on Blog

Most Popular

Leave Your Comment

Your email address will not be published
Name
Company
Mobile *
Email *
Content *