Features:
- Eight 24 V DC inputs convert field contacts and two-wire sensor states into distributed-I/O data.
- Eight protected 24 V DC outputs switch loads within one shared two-ampere output group.
- PROFIBUS DP communication, RUN/BF status, and channel LEDs connect station diagnostics with field states.
Siemens 6ES7133-0BH10-0XB0 combines acquisition and load switching in one ET 200B electronic module.
The input thresholds of 6ES7133-0BH10-0XB0 separate inactive wiring conditions from valid 24 V DC field signals.
Supported terminal blocks let 6ES7133-0BH10-0XB0 remain replaceable without disturbing permanent field wiring.
The Siemens 6ES7133-0BH10-0XB0 ET 200B 8 DI / 8 DO Digital Electronic Module may still be available for purchase and support from Apter Power beyond End-Of-Life (EOL) by the manufacturer (OEM).
Siemens 6ES7133-0BH10-0XB0 ET 200B Digital Electronic Module Manuals,Datasheets,Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Digital Input Signal Path
- Channel count: Eight input terminals acquire individual 24 V DC field states.
- Signal evaluation: Voltages from -30 to +5 V are read as off, while 13 to 30 V represents an on state.
- Sensor wiring: Two-wire sensors are supported within the stated quiescent-current limit.
- Status feedback: A green indicator reports the state of each digital input before bus transfer.
Protected Load Switching
- Channel count: Eight transistor outputs switch 24 V DC loads.
- Group limit: The combined output group is limited to 2 A at temperatures up to 60 °C.
- Fault protection: Electronic short-circuit protection limits a load fault at the output stage.
- Shutdown path: Integrated hardware shutdown removes the output commands independently of normal switching logic.
Station Communication and Status
- Bus rate: The ET 200B connection supports PROFIBUS DP up to 12 Mbit/s.
- Process exchange: Input states travel to the controller and output commands return through the same station bus.
- Run indication: The RUN LED confirms operating status of the electronic module.
- Bus fault: The red BF indicator separates communication loss from individual channel states.
Terminal Block and Installation Limits
- Terminal blocks: TB1/DC, TB1-4/DC, and TB3/DC are listed for the electronic module.
- Field conductors: Screw-type or spring-loaded terminals support permanent three- and four-wire arrangements.
- Horizontal mounting: The specified operating range extends from 0 to 60 °C.
- Other orientations: Alternative mounting positions reduce the upper operating limit to 40 °C.