Features:
- Physical system, numeric and alphanumeric keys provide local operator input without touch control.
- Direct keys and DP direct LEDs exchange configured input and output states with an S7 controller.
- PROFINET, MPI and PROFIBUS DP provide alternative controller communication paths.
The hardware and software clocks of Siemens 6AV2124-1QC02-0AX1 are synchronizable and retain time for a typically six-week period.
A speaker is installed in Siemens 6AV2124-1QC02-0AX1, while a buzzer is not fitted to the panel.
Siemens 6AV2124-1QC02-0AX1 supports configured connections to S7-1200, S7-1500, S7-300, S7-400 and SIMOTION controllers.
The Siemens 6AV2124-1QC02-0AX1 SIMATIC HMI KP1500 Comfort Key Panel may still be available for purchase and support from Apter Power beyond End-Of-Life (EOL) by the manufacturer (OEM).
Siemens 6AV2124-1QC02-0AX1 SIMATIC HMI KP1500 Comfort Key Panel Manuals,Datasheets,Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Controller-Key Data Direction
- Input mapping: Direct keys are exposed to the S7 controller as configured input I/O.
- Output mapping: DP direct LEDs receive configured output I/O states from the controller.
- Local operation: System and data-entry keys remain assigned to panel navigation and runtime commands.
- Address alignment: Key and LED addresses must agree with the project loaded in the panel.
Controller Communication Routes
- Switched segment: Two Ethernet connectors provide line-through connectivity on one network path.
- Independent segment: A separate Ethernet interface can be assigned to another network.
- Fieldbus route: The combined serial connector carries supported MPI or PROFIBUS DP communication.
- OPC UA exchange: Client and server functions add a configured runtime data path.
Engineering and Execution
- Engineering baseline: Configuration begins with WinCC Comfort V14 SP1 and the required HSP.
- Runtime platform: Windows Embedded Compact 2013 hosts the loaded Comfort Panel project.
- Screen services: Alarm handling, recipes, trends and screen objects are available to the project.
- User data: Configuration information is held in the dedicated project memory.
Record and File Destinations
- Alarm archive: Event records can be written to supported memory, USB or Ethernet locations.
- Process archive: Selected runtime values can be retained outside the internal project memory.
- File formats: Supported archive output includes CSV, TXT and RDB data formats.
- Electronic print: Runtime print-to-file output can be generated as PDF or HTML.