Features:
- Provides the rear field interface for exactly one MPC4 protection card.
- Offers four 0–10 V DAC outputs and four jumper-selectable 4–20 mA outputs.
- Passes 32 digital alarm signals to optional rack relay cards.
The selected item is the IOC4T configuration identified by ordering number 200-560-000-114.
It separates field termination from real-time processing so the MPC4 remains accessible from the rack front while plant wiring stays at the rear.
Confirm the paired slot, jumper map, external relay destinations and all six sensor circuits before energizing the rack.
Availability is subject to Apter Power inventory and sourcing confirmation.
Verified resources for Vibro-Meter 200-560-000-114:
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
- Terminates proximity, accelerometer and tachometer wiring for a paired VM600 machinery-protection processor.
- Exports calibrated analog measurements to a DCS, recorder or other plant control equipment.
- Routes selected fault and common-alarm conditions through local relays and the rack backplane.
- Four digital-to-analog converters produce calibrated 0–10 V signals from processed dynamic channels.
- Four onboard converters can deliver 4–20 mA outputs when the associated jumpers are selected.
- Voltage and current outputs appear on the rear screw terminals for connection to external systems.
- Four local relays can be assigned to selected fault, Sensor OK, Alert or Danger states in software.
- Thirty-two additional digital alarm signals can be sent across the backplane to RLC16 or IRC4 cards.
- Relay meaning depends on the active MPC4 configuration and must be verified before rewiring.
- The rear card connects to the VM600 backplane with two connectors directly behind its MPC4.
- Inputs and outputs include EMI and surge protection intended to preserve EMC performance.
- Field conductors should be identified before the removable terminal strips are transferred.