Features:
- Full-rack power: one 330 W supply supports a complete VM600 rack up to 50 °C.
- Three output rails: +5 V and ±12 V feed the backplane and installed cards.
- Flexible resilience: a second RPS6U can provide redundancy or extra derated capacity.
Select this RPS6U when the installed ABE04x rack uses the AC-input 200-582-500-02h hardware family.
Confirm the rack rear panel and PS1 or PS2 position before ordering, especially when a DC source is used with the AC version.
The installed-card load and availability target determine whether the rack needs one supply, two redundant supplies or two units sharing a higher derated demand.
Apter Power can review VM600 RPS6U SIM-330A 200-582-500-021 rack load, rear-panel interface, condition, and quotation scope.
Vibro-Meter VM600 RPS6U SIM-330A 200-582-500-021 VM600 RPS6U 330 W Rack Power Supply Manuals,Datasheets,Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
- AC input: autoranging operation covers 90-132 V AC and 180-264 V AC.
- DC operation: the AC version accepts 178-264 V DC with an appropriate rear panel.
- Backplane rails: outputs are +5 V, +12 V and -12 V DC.
- Power ceiling: all three rails share a 330 W combined maximum.
- Overvoltage: the supply latches off and requires input-power recycling after the cause is removed.
- Short circuit: automatic recovery follows removal of the short.
- Overload: automatic recovery follows removal of the excessive load.
- Temperature: natural-cooling output derating applies above the specified thresholds.
- Primary position: PS1 occupies rack slots 18 to 20.
- Second position: optional PS2 occupies slots 15 to 17.
- Redundant mode: either supply can carry the full rack load up to 50 °C.
- High-temperature mode: two non-redundant supplies can share derated rack demand.
- VM600 machinery protection: power monitoring cards used for turbine, compressor or generator protection.
- Condition-monitoring racks: feed a full ABE04x rack from one 330 W RPS6U under the stated temperature limit.
- High-availability monitoring: install two supplies where rack power redundancy is required.