- Converter-section dissipation is 19, 30, 43, 58, and 74 W at 20, 40, 60, 80, and 100% rated output
- Inverter-section dissipation is 48, 68, 91, 116, and 144 W at the same utilization points
- Internal-shunt power is excluded from those figures and must be added according to utilization
2094-AC16-M03-S has separate converter and inverter loss data so both sections can be included in the enclosure heat calculation.
Add the losses of every installed power-rail module at the expected duty point, together with the applicable internal-shunt contribution.
Install the module upright and size the enclosure and cooling system from the complete rail configuration and usable heat-transfer area.
Availability, condition, price, and shipping time for 2094-AC16-M03-S are confirmed during quotation.
Allen-Bradley 2094-AC16-M03-S Kinetix 6000 Manuals, Datasheets, Links
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
- The Integrated Axis Module occupies the leftmost position on the Bulletin 2094 power rail
- Axis modules are installed to the right in descending order of power utilization
- Place the shunt module to the right of the last axis module, followed only by slot fillers
- Rockwell Automation lists an LPJ-45SP Class J fuse for the documented 230 V configuration
- The listed molded-case circuit breaker is 140G-G6C3-C50
- Integral solid-state short-circuit protection does not replace required branch-circuit protection
- The motor-power connection accepts 10...1.5 mm² conductors (AWG 8...16)
- The published conductor strip length is 10 mm
- The specified motor-power terminal torque is 1.2...1.5 N·m
- Bulletin 2094 multi-axis systems requiring a 200/230 V-class integrated converter and first servo axis
- Compatible Kinetix 6000 power-rail systems that add axis modules to a shared DC bus
- Common-bus follower arrangements using the documented 275...375 V DC input range