Features:
- High-side output: Drives 24 VDC solenoid coils at up to 100 mA continuous current.
- Configurable behavior: Supports discrete, momentary and continuous-pulse output modes.
- Channel diagnostics: Line-fault testing distinguishes short, normal and open load conditions.
SE4302T01 is a single-channel DeltaV CHARM that provides a high-side 24 VDC output from an electronic-marshalling baseplate.
The channel can issue a maintained command, a momentary command or a continuous pulse while retaining a defined 100 mA continuous load boundary.
Integrated current limiting, line-fault testing and field-wiring disconnection help isolate load and wiring problems at the channel instead of at a shared I/O card.
For SE4302T01 24 VDC High-Side Discrete Output CHARM sourcing, Apter Power can help confirm the Emerson terminal-block and load requirements.
Emerson SE4302T01 24 VDC High-Side Discrete Output CHARM Manuals,Datasheets,Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
- Device type: 24 VDC solenoid coils and comparable low-current loads.
- Continuous output: 100 mA at 24 VDC.
- Off-state leakage: 1 mA maximum.
- Protection: The field circuit includes 200 mA current limiting and a wiring disconnect.
- Short-circuit indication: Guaranteed below a 50 Ω load.
- Good-circuit range: Guaranteed from 240 Ω to 10 kΩ.
- Open-circuit indication: Guaranteed above a 20 kΩ load.
- Test duration: The line-fault test is 200 µs.
- Discrete output: Provides a maintained on/off command for the connected load.
- Momentary output: Delivers a timed command without a separate timing relay.
- Continuous pulse: Repeats a configured output pulse for cyclic duties.
- Channel isolation: Individual CHARM assignment keeps each signal type and fault status separate in the electronic-marshalling design.
- Solenoid actuation: Commands 24 VDC solenoid coils within the continuous current rating.
- Momentary control: Supports short-duration commands used by latching or reset functions.
- Pulse duties: Generates continuous output pulses for supported cyclic control tasks.
- Relay interfacing: Works with the supported relay output terminal-block arrangement when relay contacts are required.