Ask our team:
  • Phone: +86 181 0690 9650
  • E-Mail sales1@apterpower.com
  • Lifecycle status

    Active / Available from OEM
    Apter Power supports LS IS CHARM sourcing and loop-reference review.

SS4307T01

/ 4.9
1001 reviews | Need a Specific Revision?
Emerson SS4307T01 is a DeltaV SIS intrinsically safe 4-20 mA HART analog-input CHARM for connecting field transmitters to IS electronic marshalling and safety logic.
In Stock
Ships by Wednesday, October 28
Fast Shipping Available
Get a quick price for SS4307T01
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for SS4307T01

  • Manufacturer:
    Emerson
  • Part Number:
    SS4307T01
  • Product Family:
    DeltaV
  • Product Type:
    DeltaV SIS LS IS AI 4-20 mA HART CHARM
  • Stock:
    1
  • Signal:
    4-20 mA
  • Digital Communication:
    HART
  • Safety Function:
    Galvanic isolation and energy limiting
  • Terminal Block:
    IS Standard Terminal Block
  • Status Indication:
    Bi-color Power/Integrity LED
  • Operating Temperature:
    -40 to +70°C
  • Storage Temperature:
    -40 to +85°C
  • Relative Humidity:
    5 to 95%, non-condensing
  • Protection Rating:
    IP20
  • Airborne Contaminants:
    ISA-S71.04-1985 Class G3
  • Tariff Code:
    Please confirm the destination before shipping.
  • Country of origin:
    USA
  • Place of shipment:
    Xiamen,Fujian,China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Applications Safety Protection Environmental

Features:

  • Accepts one intrinsically safe 4-20 mA HART input from a compatible field transmitter.
  • Applies galvanic isolation and energy limiting on the individual channel for hazardous-area service.
  • Uses the Power/Integrity LED to communicate actionable channel and hardware status conditions.
The SS4307T01 ordering reference belongs to the DeltaV SIS IS Electronic Marshalling family and identifies the DeltaV SIS LS IS AI 4-20 mA HART CHARM.

Intrinsically safe 4-20 mA HART transmitters connected to DeltaV SIS.

SS4307T01 is the LS IS AI 4-20 mA HART CHARM. It is mechanically prevented from installation in a non-IS terminal block.

Availability of SS4307T01 is subject to Apter Power inventory and sourcing confirmation.
Verified resources for Emerson SS4307T01: Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
  • Intrinsically safe 4-20 mA HART transmitters connected to DeltaV SIS.
  • Safety instrumented functions that benefit from channel-level galvanic isolation.
  • Electronic Marshalling cabinets requiring integrated HART diagnostics for safety inputs.
  • Use the LS IS CHARM only within the approved DeltaV SIS IS Electronic Marshalling architecture.
  • Complete the loop entity-parameter calculation for the connected hazardous-area instrument.
  • Follow the SIF lifecycle and installation requirements associated with the project approvals.
  • Read the Power/Integrity LED to distinguish normal, unconfigured, wiring-fault, and internal-fault states.
  • Use HART device information to diagnose field conditions before they cause a spurious trip.
  • Rely on channel isolation so a severe wiring fault is contained at the affected LS IS CHARM.
  • Operate the hardware from -40 to +70°C under the common component specification.
  • Maintain 5 to 95 percent non-condensing humidity and Class G3 contaminant protection.
  • Install the IP20 hardware in a suitable field enclosure for the actual location.
Description
SS4307T01 is an Emerson DeltaV SIS intrinsically safe Logic Solver analog-input CHARM for 4-20 mA HART signals. It performs channel signal characterization, galvanic isolation, and energy limiting for an IS Electronic Marshalling channel.

The LS IS CHARM brings HART device diagnostics into the CHARM Smart Logic Solver and provides channel-level fault isolation. A bi-color Power/Integrity LED reports normal, unconfigured, wiring-fault, or internal-fault states.

Install SS4307T01 only with the light-blue IS terminal block and IS CHARM baseplate architecture. Verify loop entity parameters, field-device approval, keying, wiring, and safety-system documentation before commissioning.
Alternative Names
SS4307T01 SS4307 T01 SS4307-T01 Emerson SS4307T01 DeltaV SIS SS4307T01 SS4307T01 IS AI 4-20 mA HART CHARM Emerson DeltaV SIS LS IS Analog Input CHARM
Technical notes
SS4307T01 is the LS IS AI 4-20 mA HART CHARM. It is mechanically prevented from installation in a non-IS terminal block.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
Which signal is handled by SS4307T01?
It is the LS IS analog-input CHARM for 4-20 mA signals with HART.
What isolation is provided at the channel?
The CHARM supplies galvanic isolation, energy limiting, and single-channel fault isolation.
Can SS4307T01 fit a standard non-IS terminal block?
No. The IS CHARM and terminal hardware are mechanically different to prevent that installation.
What does a blinking red Power/Integrity LED indicate?
Emerson identifies it as a detected field-wiring fault.
How does HART information reach the safety system?
Integrated HART data is brought into the CHARM Smart Logic Solver for diagnostics and logic use.
Which safety checks precede channel commissioning?
Validate entity parameters, terminal type, field-device approval, keying, polarity, and the SIF design.